Want this question answered?
The easiest way to input a fraction while calculating is to simply divide the top of the fraction by the bottom. So four fifths would be (4/5). To convert an answer into a fraction, such as .125, press the math button and select >Frac. .125>frac = (1/8)
20 percent off 125 = 10020% off of 125= 20% discount applied to 125= 125 - (20% * 125)= 125 - (0.20 * 125)= 125 - 25= 100
125 x 125 = 15625
1*125=125 or 5*25=125
The GCF is 125.
Yes, no problem at all going to a larger ampacity of wire. Larger size wire yes, smaller size wire no.
If you know the size of the load to be served, multiply it by 125% ( times 1.25) and choose a conductor that is rated for that ampacity or higher.
The minimum score for a Pope and Young Whitetail buck is 125 inches.
the minimum wage of a filipino worker is 125 pesos only!!
Power Factor is one of most significant parameter in calculating AC Power. As we know it is cosine of angle between AC Voltage and Current it comes in picture while calculating power in AC circuits Power In AC (P) = Voltage (V) X Current (V) X Power Factor Let us take an example of Power with Power factor and without power factor for same circuit. Let Us assume V = 125 Volts I = 1 Amp Power Factor = 1 Then P = 125X1X1= 125 Watts But for any circuit when Power factor is below 1, to execute same power, Circuit has to draw more current. for example P = 125X 1.25 X 0.8 = 125 Watts In first example power factor of the circuit was unity = 1 and in that condition current of the circuit was 1 amp whereas in second example power factor of the circuit is 0.8 due to which current of the circuit increases to 1.25 amp to execute the same power. Now due to increase in current of the circuit many factors are affected like heat loss, Conductor's specification , Class of insulation etc. Thus it can be concluded after going through above explanation that power factor play a significant role in AC power calculation as well as in actual practices.
Electricians must be extra careful when calculating power requirements for circuits that will run motors because motors have high starting currents that can overload the circuit if not accounted for. This can lead to overheating, tripping of circuit breakers, and possible damage to the motor or other components. Properly calculating power requirements ensures safe and efficient operation of the motor and the circuit.
The address of the Ninth Judicial Circuit is: 125 S Grand Avenue, Pasadena, CA 91105-1643
It is 125*8 = 1000
FMF Gnarly pipe and a Pro Circuit r304 silencer
all voltage is plus or minus 10% of rating
Around 150- 175. 125 at minimum.
Yes if going at at least a minimum of 125 mph in a certain cpot