To answer this question the following is needed. The voltage of the circuit, whether single or three phase. To calculate whether additional de-rates have to be applied the type of wiring system should be stated, overhead, direct bury or conduit system.
A single conductor single phase will need a #3 copper conductor and will limit the voltage drop to 2.93% when supplying 30 amps for 250 feet at 120 volts.
A single conductor single phase will need a #6 copper conductor and will limit the voltage drop to 2.76% when supplying 30 amps for 250 feet at 240 volts.
A single conductor single phase will need a #8 copper conductor and will limit the voltage drop to 2.16% when supplying 30 amps for 250 feet at 480 volts.
A single conductor single phase will need a #10 copper conductor and will limit the voltage drop to 2.62% when supplying 30 amps for 250 feet at 600 volts.
A single conductor three phase will need a #10 copper conductor and will limit the voltage drop to 2.84% when supplying 30 amps for 250 feet at 480 volts.
A single conductor three phase will need a #10 copper conductor and will limit the voltage drop to 2.27% when supplying 30 amps for 250 feet at 600 volts.
<<>>
Single phase or 3 phase it doesn't matter. 30 amps is 30 amps.. Above your head or in the ground its still 30 amps.. 10awg is usually good for 30 amps but, with this voltage drop I would run 6awg.
For a 50 amp service running 800 feet, you would typically need to use a wire size of at least 6 AWG copper or 4 AWG aluminum to minimize voltage drop and ensure the circuit can handle the load safely. It is recommended to consult local electrical codes and a qualified electrician for specific recommendations based on your exact requirements.
The National Electrical Code is a valuable source to find answers to this type of question since there are many more factors to selecting proper wire size than just distance and current requirements.
Also, you should check with you local building inspection department to determine if there are stat or local code requirements that exceed the National Electrical Code.
This is a voltage drop question and a voltage needs to be stated.
We recommend using a #6 copper wire for the connection between the breaker box and the earth ground rod. This size wire is commonly used for grounding purposes and is sufficient for carrying the electrical current safely to the ground rod. Be sure to consult with a qualified electrician to ensure the proper materials and installation for your specific situation.
A 3/0 copper conductor would allow you up to 100 feet at 800 Amps with only 5 percent voltage drop, assuming 240-volt service. If it were a 3-phase 480-volt service, you could go more than 23 feet with only a 5 percent drop. <<>> The size of conductors for an 800 amp service could be sized in several ways. Using a single conductor is out of the question as the size will be impossible to bend or handle. A 2000MCM wire only has a rating of 775 amps. Most high amperage services will use parallel runs to add up to the required amperage. A parallel run of 600 MCM will give you a total of 910 amps. A triple parallel run of 300 MCM will give you a total of 885 amps. A quad parallel run of 3/0 will give you an amperage of 840 amps. The key here is to find the most economical way of installing the service. Take into account the availability of triple barrel or four barrel lugs, wire costs for the larger sizes and the labour to man handle the larger sizes into the main switch. These size services that I have installed, the customer opted for the four barrel lugs with 3/0 wire. The 3/0 wire is a readily available item even though the lugs may have to be a special order.
For a 1200 amp service, you should use a copper ground wire of at least 3/0 AWG or an aluminum wire of at least 250 kcmil to meet the National Electrical Code requirements. It's always recommended to consult with a licensed electrician to ensure the proper sizing and installation of the ground wire.
There are 12 inches in one foot. Therefore, 800 inches is equal to 800/12 = 66.6 recurring (that is, 66.666..) feet or 66 feet 8 inches.800 inches = 66.66 feet
A 500 MCM copper conductor will limit the voltage drop to 3% or less when supplying 50 amps for 800 feet on a 120 volt system. 500 MCM wire diameter is 1/2 inch. As you can see there will be trouble getting that size wire into a 50 amp breakers lug. On installations like this to offset the voltage drop at such a low voltage, a transformer should be used at both ends. The first transformer to raise the voltage and the second transformer to lower it at the 800 foot end. If you use two 480 volt transformers a #1 wire can be used between them. A #1 copper conductor will limit the voltage drop to 3% or less when supplying 50 amps for 800 feet on a 480 volt system. By increasing the voltage you can see that a smaller wire size can be used. On an installation of this nature, a primary line should be brought to the RV site and a service distribution panel established at that point and any RV vehicles can then be fed from that service.
This is a voltage drop question and a voltage needs to be stated.
We recommend using a #6 copper wire for the connection between the breaker box and the earth ground rod. This size wire is commonly used for grounding purposes and is sufficient for carrying the electrical current safely to the ground rod. Be sure to consult with a qualified electrician to ensure the proper materials and installation for your specific situation.
There are two distinct questions here. To determine the wire size to carry 15000 volts the circuits load amperage must be stated. The wire size for a 550 amp service is, an 800 MCM copper conductor with an insulation factor of 90 degrees C. This conductor is rated at 555 amps. Parallel 250 MCM will give you a total capacity of 580 amps. A triple run of 2/0 will give you a total capacity of 585 amps.
A 3/0 copper conductor would allow you up to 100 feet at 800 Amps with only 5 percent voltage drop, assuming 240-volt service. If it were a 3-phase 480-volt service, you could go more than 23 feet with only a 5 percent drop. <<>> The size of conductors for an 800 amp service could be sized in several ways. Using a single conductor is out of the question as the size will be impossible to bend or handle. A 2000MCM wire only has a rating of 775 amps. Most high amperage services will use parallel runs to add up to the required amperage. A parallel run of 600 MCM will give you a total of 910 amps. A triple parallel run of 300 MCM will give you a total of 885 amps. A quad parallel run of 3/0 will give you an amperage of 840 amps. The key here is to find the most economical way of installing the service. Take into account the availability of triple barrel or four barrel lugs, wire costs for the larger sizes and the labour to man handle the larger sizes into the main switch. These size services that I have installed, the customer opted for the four barrel lugs with 3/0 wire. The 3/0 wire is a readily available item even though the lugs may have to be a special order.
For a 1200 amp service, you should use a copper ground wire of at least 3/0 AWG or an aluminum wire of at least 250 kcmil to meet the National Electrical Code requirements. It's always recommended to consult with a licensed electrician to ensure the proper sizing and installation of the ground wire.
800 square feet
Feet and linear feet are the same unit of measurement. Therefore, 800 linear feet is equal to 800 feet.
Answer: 480,000 ft² = 11.0192 acres
Don't know what you mean by actual size. It could be 80 x 10, but could be any shape.
800 x 3 feet per yard = 2400 feet
There are 12 inches in one foot. Therefore, 800 inches is equal to 800/12 = 66.6 recurring (that is, 66.666..) feet or 66 feet 8 inches.800 inches = 66.66 feet