No. The sub panel is wired that same as an ordinary three wire load. The three wire is connected the sub panels terminal points as red to L1, black to L2, white to the neutral bar and the ground wire in the cable set to the ground bar. The one thing that has to be done is the bonding screw that bonds the neutral bus to the panels metallic enclosure has to be removed. The electrical code states that there is only one place that the ground is joined to the neutral bar and that is at the service entrance point into the main distribution panel.

User Avatar

Wiki User

9y ago
This answer is:
User Avatar
More answers
User Avatar

AnswerBot

6d ago

No, neutral and ground wires should be kept separate in a service panel to prevent any potential safety hazards and ensure proper grounding. The neutral wires connect to the neutral bus bar, while the ground wires connect to the ground bus bar. Mixing them on the same bus bar can create potential electrical hazards.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

No, in any distribution panel there are individual bars for each termination. The ground buss is in direct contact with the metal enclosure. The neutral is isolated from the metal enclosure. The only place where the two come into contact with each other is where a bonding screw protrudes through the neutral bar and into the metal enclosure.

This answer is:
User Avatar

User Avatar

Wiki User

9y ago

You only connect neutral and ground together at the MAIN PANEL, not at sub panel. The reason is that you need a single ground so as not to create what are called ground loop currents.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

yes

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can neutral and ground wires be connected to the same buss bar in a service panel?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

How do you know what wire is ground on 200 amp service?

In a 200 amp service panel, the ground wire is typically a bare copper wire or green insulated wire. It is connected to the ground bar within the panel. Make sure to consult the manufacturer's instructions or a licensed electrician for guidance specific to your installation.


In the typical home electrical panel installation the main ground wire is connected directly from a ground rod driven into the ground to the?

main grounding bar inside the electrical panel. This connection is crucial for redirecting excess electrical currents safely into the ground and preventing electrical hazards within the home. The ground rod helps to dissipate electrical charges and provides an additional path for fault currents to travel in case of a short circuit.


Why do you isolate the neutral?

If you are working with a sub panel, there are a few reasons to isolate the neutral. Firstly, currents will then return to the main panel and service ground.


Should neutral wire of lamp be connected to the 3amp or the 6 amp side of a canopy switch?

You should never switch the neutral wire. The neutral of the appliance should be connected directly to the neutral wire leading to the service panel neutral bar.


Can you connect a ground to a neutral bar?

In any distribution panel there are individual bars for each termination. The ground buss is in direct contact with the metal enclosure. The neutral is isolated from the metal enclosure. The only place where the two come into contact with each other is where a bonding screw protrudes through the neutral bar and into the metal enclosure.

Related questions

How do you know what wire is ground on 200 amp service?

In a 200 amp service panel, the ground wire is typically a bare copper wire or green insulated wire. It is connected to the ground bar within the panel. Make sure to consult the manufacturer's instructions or a licensed electrician for guidance specific to your installation.


Is neutral connected to earth in main panel?

Answer for USA, Canada and countries running a 60 Hertz supply service.Yes, the neutral is connected to a system ground in the main distribution panel.


In the typical home electrical panel installation the main ground wire is connected directly from a ground rod driven into the ground to the?

main grounding bar inside the electrical panel. This connection is crucial for redirecting excess electrical currents safely into the ground and preventing electrical hazards within the home. The ground rod helps to dissipate electrical charges and provides an additional path for fault currents to travel in case of a short circuit.


What is rod earthing?

It is the installation of ground rods at a service entrance distribution to bring the relative resistance to ground to be within 5 ohms of the utility's distribution network. This grounding system is then connected to the service distribution with a calculated size wire and connected to the distribution at a point within the distribution panel, where the service neutral wire joins the neutral bus bar.


Why do you isolate the neutral?

If you are working with a sub panel, there are a few reasons to isolate the neutral. Firstly, currents will then return to the main panel and service ground.


Do you need a grounding rod at a subpanel on a detached building?

Yes. The panel must be grounded with its own grounding rod. The ground will not be provided with the feeders to the panel, these will only contain your phase wires and neutral. Also make sure that any subpanel installed does not have the neutral bonded to ground. This should only be done at the main panel where the electrical utility service is connected.


What is an electrode conductor?

It is the conductor that is used in service distribution panels that bonds the distribution panel's neutral bus bar to the ground electrode (rod). This brings all of the distribution panel neutrals that are connected to the same supply system to the same potential, that being zero. Should a supply service neutral open this ground wire will maintain the systems integrity until repairs can be made.


In typical home electrical panel installation the main ground wire is connected directly from a ground rod driven into the ground to the?

In North American residential homes, there are 3 wires coming from the utility company, two "hots" and neutral. The two "hot" conductors get connected to the main breaker. The neutral gets connected to the neutral bus bars located along the sides of the breaker box. There is a set screw that is placed in the neutral bar that screws into the distribution panel enclosure thereby bringing the potential of the neutral bars down to zero. The wire from your ground rod is also connected to the neutral bus bar, and thereby it is connected to the neutral from the power company. This is also often bonded to the copper cold water Plumbing in the house if the home is not plumbed in PVC water pipe. White circuit wires are then connected to the neutral bus bars. Also in the distribution panel are ground bus bars. The ground wires from circuit cables are connected to these grounding bars. Do not under any circumstance terminate the white and bare ground wires together. Ground wires to the ground bar and white wires to the neutral bar.


Should neutral wire of lamp be connected to the 3amp or the 6 amp side of a canopy switch?

You should never switch the neutral wire. The neutral of the appliance should be connected directly to the neutral wire leading to the service panel neutral bar.


Can you connect a ground to a neutral bar?

In any distribution panel there are individual bars for each termination. The ground buss is in direct contact with the metal enclosure. The neutral is isolated from the metal enclosure. The only place where the two come into contact with each other is where a bonding screw protrudes through the neutral bar and into the metal enclosure.


Why do white wire mark 120v?

Because the white wire on a 120 volt circuit is the neutral wire that is connected to the silver screw on outlets and switches. It is connected to the neutral bar in the service panel.


Can the bare grounded neutral conductor of a service be buried directly in the ground?

No, the bare grounded neutral conductor of a service should not be buried directly in the ground. It should be installed above ground or within a suitable raceway or conduit to provide proper protection against damage or corrosion.