You can use the wire rated for 20 amps on a 15 amp receptacle but you can not use a 20 amp fuse on any device rated at 15 amps.

This is a tricky part of the code about receptacle outlets, You can use a 15 amp duplex outlet on a 20 amp circuit. (duplex outlet two devices can plug in) If it is a single outlet then the outlet must be rated 20 amp. NEC table210.21(B)(3).

============

A 15 amp duplex receptacle can be wired to a 20 amp rated circuit. This means the breaker OR fuse protecting the circuit can be rated 20 amps if the wire is also rated at 20 amps (12 AWG). --Sparkfighter

User Avatar

Wiki User

13y ago

What else can I help you with?

Related Questions

What does the 20 amp power outlet fuse do on a 1999 Dodge Durango?

What does the 20 amp power outlet fuse do on a 1999 dodge durango


Can you replace a 30 amp fuse with a 15 amp fuse?

Not a good idea. The 15 amp fuse will be protection a #14 wire which is rated for 15 amps maximum capacity. By changing the 15 amp fuse to a 30 amp fuse you would then be allowing 30 amps maximum capacity on a #14 wire. By doubling the load the extra heat generated on the smaller wire could be enough to melt the insulation from the wire and that could cause the wire to short out. If the wire shorts out inside the wall it means the removal of the wall board to replace the wire to restore the circuit to an operational condition. The proper wire sizing for a 30 amp fuse is, #10 copper wire with an insulation rating of 90 degrees C.


Can a 15 amp breaker that supplys an outlet be replaced it with a 30 amp without starting a possible fire?

Not without moving up two wire sizes from a #14 copper wire rated for 15 amps to a #10 copper wire rated for 30 amps.


How many watts is a 240 volt 20 amp fuse rated for with 12 gauge wire?

4800


If your fuse box supports 20 amp fuses can you replace one current 15 amp fuse with a 20 amp fuse?

The purpose of a fuse it to protect the wire that goes to the load. A 15 amp fuse protects a #14 gauge wire. A 20 amp fuse protects a #12 gauge wire. To answer your question if the wire size is #12 coming from the 15 amp fuse now then it can be upped to 20 amp fuse. If it isn't then you are taking the risk of overloading the #14 wire with a 20 amp fuse. This can lead to insulation failure of the #14 wire, overheating with the possible outcome of a fire breaking out somewhere in the circuit.


What is thicker a 8amp fuse wire or a 15amp wire?

The 15 amp fuse.


What colour goes to fuse in American wire?

The standard color coding for fuses in American wire is as follows: 15-amp fuse: blue 20-amp fuse: yellow 30-amp fuse: green


Can 50 Amp breaker replace 45 Amp breaker?

Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.


How thick is a 30 amp fuse wire?

A 30 amp fuse wire typically has a diameter of around 0.08 inches (2 millimeters).


How do you choose the right fuse for the job?

The correct size fuse needed is based on the size wire used in the circuit. The size wire needed is based on the load that will be applied to the circuit. 1. AWG 14/2 wire = 15 amp fuse 2. AWG 12/2 wire = 20 amp fuse 3. AWG 10/2 wire = 30 amp fuse 4. AWG 8/2 wire = 40 amp fuse


Can 10-2 wire be used for an outlet?

Yes, 10-2 wire can be used for an outlet. The 10-2 wire consists of a black hot wire, a white neutral wire, and a ground wire. Ensure that the wire gauge matches the amperage requirements of the outlet and that it is installed according to local electrical codes.


Can 600v wire works 30 amp fuse?

What size is the wire? AWG 10, 600V is rated for 30 amps. Any AWG less than 6 would also be ok for a 30 amp circuit....