A #8 copper conductor with an insulation factor of 60 degrees C is rated at 40 amps. For a built in safety factor, a #8 conductor with an insulation factor of 75 or 90 degrees C has a rating of 45 amps.
No. The two appliances usually have dedicated circuits. The range will have a two pole 40 amp breaker and be fed with a 3-C #8 copper cable. The dryer will have a 30 amp two pole breaker and be fed with a 3-C # 10 copper cable. As you can see by powering a 40 amp device from a 30 amp breaker, full operation of the range will trip the 30 amp breaker.
No, it is not recommended to replace a 35 amp breaker with a 40 amp breaker for an AC unit. Breakers are designed to protect the circuit and the equipment, so using a higher rated breaker can lead to overheating and potential damage. It is best to use the correct amperage rated breaker for the equipment.
No. The 20 amp breaker is probably protecting a #12 wire. Connecting a 40 amp breaker to the 20 amp #12 wire would seriously overload the #12 wire. This means that if the load increased to a full 40 amps the insulation on the smaller size wire would most likely melt off and the wire could short out.
The formula you are looking for is I = W/E.
No, because if you switch a 50-amp load on, it will blow a 40-amp circuit breaker if the load exceeds 40 amps, which is likely.
The appropriate wire size for a 40 amp breaker is typically 8 AWG (American Wire Gauge).
The recommended wire size for a 40 amp breaker is typically 8 AWG (American Wire Gauge).
7.2kW shower = 32 Amp fuse = 6 mm2 cable size7.5kW shower = 40 Amp fuse = 10 mm2 cable size8.5kW shower = 40 Amp fuse = 10 mm2 cable size9.5kW shower = 40/45 Amp fuse = 10 mm2 cable size10.5kW shower = 45 Amp fuse = 16mm2 cable size
In North America the standard sizes for breakers are 15, 20, 30, and 40 amps. The 15 amp size breaker is used in general circuit wiring. The 20 amp size breaker is used for dedicated appliance receptacles, hot water tank and baseboard heating. The 30 amp size breaker is used for a clothes dryer. The 40 amp size breaker is used for the electric range.
No. The two appliances usually have dedicated circuits. The range will have a two pole 40 amp breaker and be fed with a 3-C #8 copper cable. The dryer will have a 30 amp two pole breaker and be fed with a 3-C # 10 copper cable. As you can see by powering a 40 amp device from a 30 amp breaker, full operation of the range will trip the 30 amp breaker.
For a 40 amp breaker, a wire size of at least 8 AWG (American Wire Gauge) should be used to ensure safe and proper electrical conductivity.
Usually 30 amp
No, it is not recommended to replace a 35 amp breaker with a 40 amp breaker for an AC unit. Breakers are designed to protect the circuit and the equipment, so using a higher rated breaker can lead to overheating and potential damage. It is best to use the correct amperage rated breaker for the equipment.
No. The 20 amp breaker is probably protecting a #12 wire. Connecting a 40 amp breaker to the 20 amp #12 wire would seriously overload the #12 wire. This means that if the load increased to a full 40 amps the insulation on the smaller size wire would most likely melt off and the wire could short out.
A 40-50 amp breaker is typically used for an electric range.
The formula you are looking for is I = W/E.
If you are referring to house wiring then the answer is no. A breaker protects the wire size that is connected to the breaker. In home wiring most homes are wired with a #14 wire which is rated at 15 amps. That is why the wire is protected by a 15 amp breaker. The correct wire size to connect to a 40 amp breaker is a #8. This size wire is too large to connect to receptacles an light fixture terminals.