A 3/0 copper conductor with an insulation rating of 75 or 90 degrees C is rated at 200 and 210 amps respectively.

A 3/0 copper conductor will limit the voltage drop to 2% or less when supplying 200 amps for 80 feet on a 240 volt system.

User Avatar

Wiki User

12y ago

What else can I help you with?

Related Questions

How many feet away does the electrical box have to be from the actual meter?

It has to be at least eighty feet away Not it has to be fifteen


What is the distance needed from an electrical panel to the edge of a roof?

There is no specific distance specified in the code book. The meter stack has to be on the outside of the building and some times this means bringing it through the eave end of the roof line. The connection point has to be 15 feet high as a minimum. The utility meter has to be at head height on the outside wall for the meter reader to see and read it. On the lower end of the meter stack is the electrical panel. As you can see the distances will change in every circumstance depending on where the electrical panel is placed. The electrical panel can not be placed any further in the building from the outside wall than ten feet.


How close can a electrical panel be to a gas meter?

According to the National Electrical Code (NEC), an electrical panel should be installed at least 3 feet away from a gas meter. This distance helps prevent potential hazards and allows for safe access during emergencies or maintenance. Local codes may vary, so it's important to check with local regulations or a qualified electrician for specific requirements in your area.


What is the recommended wire size for a 60 amp sub panel located 100 feet away?

For a 60 amp sub panel located 100 feet away, it is recommended to use a 6-gauge wire size to ensure proper electrical conductivity and safety.


How long can service entrance wire be to panel?

In the CEC (Canadian Electrical Code) the code states that from the outside meter base to the first over current device that, the run can be no longer than 20 feet.


What is the standard height for an electrical panel in a residential building?

The standard height for an electrical panel in a residential building is typically around 4 to 5 feet above the floor level.


Can you have a sub panel in a clothes closet?

No, nor under a stairwell. The electrical code stipulates that there has to be 3 feet or 1 metre in front of an electrical panel for clearance for easy access. The panel being in the closet does not fit this criteria.


What is the maximum height allowed for an electrical panel installation according to safety regulations?

The maximum height allowed for an electrical panel installation according to safety regulations is typically around 6 feet 7 inches from the floor to the center of the panel.


What is the maximum height allowed for an electrical panel installation according to building codes and regulations?

The maximum height allowed for an electrical panel installation according to building codes and regulations is typically around 6 feet 7 inches from the floor to the center of the panel.


How far away should a desk be from an electrical panel?

In front of any electrical equipment, there has to be a free space of 1 metre or 3 feet. This is so that the equipment can be worked on without any obstructions being in the way. A clean work space is a safe work space.


How close can your washer be to your electrical panel?

Typically, washers should be positioned at least 6 feet away from electrical panels to ensure proper ventilation and access for maintenance. It's important to follow manufacturer guidelines and local building codes to ensure safety and compliance.


Exterior electrical service should be 3 feet away from what?

Windows that can be opened.