Your service provider will give you that information The size will depend on: A) how close to the transformer are you. B) copper or aluminum C) Yes, you have a 400amp service but what will your actual peak amp usage be. D) Underground or overhead.
For a 3KW motor with a 350-meter run and 240V supply voltage, you would typically need a cable size of around 16mm² for proper voltage drop considerations and to prevent overheating. It's recommended to consult with a qualified electrician or use a voltage drop calculator to determine the exact cable size needed for your specific installation.
The formula you are looking for is I = W/E.
9.5 Kva is the is the same as 9500 watts. Formula for Amps = Watts/Voltage. As you now can see you didn't give me any voltage so that the amperage can be calculated. Without the amps the wire size can not be calculated. Reply in a discussion if you are interested in an answer.
The question is one of voltage loss. The goal is to have enough ampacity in the selected conductors to run the maximum load with only 3 percent voltage drop, caused by the resistance inherent in the wires. Plug your numbers into a voltage drop calculator online and see what pops out. At 120 volts you would get 3.1 percent drop using 3/0 wire. At 240 volts you could drop down three sizes to #1 AWG for 3.1 percent at max load, or 1/0 size for 2.5 percent drop at max load. Assuming copper wire at normal conditions of temperature.
The main piece of information needed is the load wattage or amperage that will be connected to the power supply. Once this is known the power supply of a greater size that the load should be chosen. Also with this information the size of the wires can be calculated from the power supply to the load. Too small a wire will create a voltage drop at the load end of the circuit. This will cause under performance of the load.
16 mm to 18 mm
Ohms law says that watts are equal to volts times amps. 240v X 13.5a = 3240 va VA / 1000 = Kva So, your load requires 3.24 Kva. The transformer should have a rating greater than this as a safety factor, so you would choose the next larger size, in this case probably a 5 Kva transformer with a 480v primary and a 240v secondary. Your local electrical codes may require a larger safety factor, so you would want to consult them before buying the transformer!
The size of the generator is based on the size of the load you want to supply. Size up the load in watts or amps along with what phase (single or three) and voltage that the load requires. These are needed to give a complete answer.
The recommended wire size for a 240V electrical circuit is typically 10-gauge wire.
For a 3KW motor with a 350-meter run and 240V supply voltage, you would typically need a cable size of around 16mm² for proper voltage drop considerations and to prevent overheating. It's recommended to consult with a qualified electrician or use a voltage drop calculator to determine the exact cable size needed for your specific installation.
The recommended wire size for a 240V 30 amp circuit is typically 10 gauge wire.
The recommended wire size for a 30 amp 240v circuit is typically 10 gauge wire.
The appropriate wire size for a 240V 30 amp circuit is typically 10 gauge wire.
To span a distance of 20 feet, a lumber beam of at least 2x10 size is typically needed for adequate support.
The recommended wire size for a 240V 50 amp circuit is typically 6 AWG copper wire.
The appropriate wire size for a 240V 50 amp circuit is typically 6 AWG copper wire.
The appropriate wire size for a 50 amp 240v circuit is typically 6 AWG copper wire.