answersLogoWhite

0

This may be do to corrosion or arcing at a connection point. Look for corrosion or blakened spots where the wires connect to the outlet, wire nuts, and breaker. Look also at the point were the breaker makes contact with the bus bar. If there are other outlets on the same circuit as is common, and the other outlets are working fine. Than you can skip checking the braker and will need to check the outlets on that same circuit where the problem outlet is fed power from. This is assuming that there is good power coming from the bus bar in the power panel. What you are looking for is something that can make resisance in the circuit. A broken wire inside it's jacket is also a possiibillity. Don't forget to check the neutral (usually white wire) for a problem. The most important thing is safety, shut off the power before checking the circuit and remember that the bus bars in the power panel are HOT with 110 and 110 or 220 volits. Something is using that power you are not getting to your appliance, and more than likely is turning it into heat. If you are not comfterable checking for bad connections yourself, call an electrician. It is very likely this is a fire hazard.

User Avatar

Wiki User

17y ago

Still curious? Ask our experts.

Chat with our AI personalities

BeauBeau
You're doing better than you think!
Chat with Beau
TaigaTaiga
Every great hero faces trials, and you—yes, YOU—are no exception!
Chat with Taiga
JudyJudy
Simplicity is my specialty.
Chat with Judy
More answers

A whole room of wall outlets not working could be due to a tripped circuit breaker, a blown fuse, a faulty outlet, or a wiring issue. It is recommended to check the circuit breaker panel, inspect each outlet for damage, and consider contacting a professional electrician for further diagnosis and repair.

User Avatar

AnswerBot

10mo ago
User Avatar

If you are asking why one outlet in a circuit doesn't work while others do in the same circuit then it is likely a wiring problem. Sometimes a wire nut comes loose and wires do not make contact. Often there is a GFCI circuit breaker outlet in a kitchen or bathroom may control multiple outlets. Make sure a GFCI outlet isn't tripped. A GFCI will have two buttons - TEST and RESET. Look for such an outlet nearby and press reset.

User Avatar

Wiki User

15y ago
User Avatar

It would because the outlets are connected by a series circuit.

User Avatar

Wiki User

15y ago
User Avatar

Add your answer:

Earn +20 pts
Q: Why would a whole room of wall outlets not work?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

Can you use 15 amp wall outlets in living room?

Yes, you can use 15 amp wall outlets in a living room. These outlets are suitable for most common household devices and appliances that don't require high power consumption. However, if you plan to connect high-power devices like air conditioners or space heaters, you may need to install dedicated 20 amp outlets.


What is the correct way to figure out the location of outlets in a room?

The best way to identify the location of outlets in a room is to visually inspect the walls for the outlets themselves. Outlets are typically placed around 12-18 inches from the floor and spaced regularly around the room. You can use a stud finder to help pinpoint the general location of outlets since they are often installed near studs.


Can two electrical outlets be in same stud wall cavity in a fire wall.?

It is generally recommended to avoid having electrical outlets in the same stud wall cavity in a fire wall. If outlets are installed in the same cavity, they should be separated by a fire-rated partition or barrier to prevent fire spread. It is best to consult with a qualified electrician and follow local building codes to ensure proper installation.


Should an outlet located at 7 feet up the wall from the floor used to power a light fixture be included in wall space requirements?

I have never heard of wall space requirement in the electrical terminology. There is a code rule for the positioning of receptacle outlets around a room. This type of outlet has to be counted as a device when estimating the number of outlets that can be installed on one circuit. If you are talking about horizontal placement of electrical boxes at 300 mm floor level, then this outlet will not be included in that measurement.


Should an outlet located at 7 feet up the wall from the floor used to power a light fixture be included in wall space requirement?

I have never heard of wall space requirement in the electrical terminology. There is a code rule for the positioning of receptacle outlets around a room. This type of outlet has to be counted as a device when estimating the number of outlets that can be installed on one circuit. If you are talking about horizontal placement of electrical boxes at 300 mm floor level, then this outlet will not be included in that measurement.