In the United States, the NEC requires that runs of conduit be continuous and connections be made wrench tight. If done properly this provides added grounding protection to your circuits. If a connection is left loose, that added grounding protection does not exist.
There are times when threaded connections simply won't thread completely. This may require that the conduit threads be "run" with a threader to remove whatever is preventing this from happening. With experience you learn what is acceptable or not acceptable. Generally, if the connection is "wrench tight" and is otherwise secure, that is sufficient.
In the United States, the NEC requires that runs of conduit be continuous and connections be made wrench tight. If done properly this provides added grounding protection to your circuits. If a connection is left loose, that added grounding protection does not exist. There are times when threaded connections simply won't thread completely. This may require that the conduit threads be "run" with a threader to remove whatever is preventing this from happening. With experience you learn what is acceptable or not acceptable. Generally, if the connection is "wrench tight" and is otherwise secure, that is sufficient.
In the United States, the NEC requires that runs of conduit be continuous and connections be made wrench tight. If done properly this provides added grounding protection to your circuits. If a connection is left loose, that added grounding protection does not exist. There are times when threaded connections simply won't thread completely. This may require that the conduit threads be "run" with a threader to remove whatever is preventing this from happening. With experience you learn what is acceptable or not acceptable. Generally, if the connection is "wrench tight" and is otherwise secure, that is sufficient.
what is meant by pull back effect when pulling in electric cables in conduit
There are several projects that can be done to find out the effect of coupling on rust. One example would be to experiment on several different types of alloys to see which rusts least.
Using the cosine law of illumination, if two cables are laid at right angles, since cos 90 = 0, the coupling will be the lowest possible. If the two cables are laid parallel, the coupling will be maximum. Be aware that shielding or twisting of cable pairs reduces the coupling effect.
the circuit will pass waves of a lower frequency
You can have only one current carrying conductor in a conduit, but that conduit must have a slot to relieve the eddy currents that will be created by the transformer effect created by the conductor. It is better to run the neutral or opposite conductor along with the hot conductor together in the same conduit, or through the same penetration, so as to minimize this effect.
increase the balance of the liability account :)
couplings are used to join sections of long transmission shafts. couplings are also used to connect the shaft of a driving machine to the shaft of a separately built machine so as to give an effect of continuous shaft. the general classification of couplings is as given under: 1. rigid coupling 2. flexible coupling 3.Camlock coupling
Loading of Rc coupled amplifier occurs, if you doesnt use coupling capacitors...... If avoiding input coupling capacitor the amplifier will load the function generator.. For more details go to http://mycircuits9.blogspot.com
Coupling is an important metric. If the module P. is tightly coupled to module Q. then a change to module P. may require a corresponding change to module Q. If this change is made, as required, during integration or postdelivery maintenance, then the resulting product functions correctly; however, progress at that stage is slower then would have been the case had coupling been looser. It has been shown that the stronger (more undesirable) The coupling, the greater the fault proneness. In other words, it is easy to believe that strong coupling can have a deleterious effect on maintainability.
They can be either separated or combined. What governs the choice is the size of the service and the conductors feeding the service and the ability to physically connect metering equipment to larger size conduits. When paralleling conduits make sure all the phase wires are in their individual conduits to cancel the field effect of the wires. Eg. conduit 1 - L1 + L2 + N , conduit 2 - L1 + L2 + N. Likewise with three phase, conduit 1 - L1, L2, L3, conduit 2 L1, L2, L3.