in most circumstances the ampacity of a 10 awg wire is 30 amps but should not be loaded to more than 80% of its capacity as a rule of thumb. there are certain instances were these values can change but like i said under "normal" conditions 30amps
for residential use 2/0 copper or 4/0 aluminum, if your talking long distances then you need to up size for voltage drop
Yes, a 20 amp breaker requires AWG # 12 copper wire. A 15 amp breaker requires AWG # 14 copper wire.
A #8 copper conductor with an insulation factor of 75 or 90 degrees C are both rated at 45 amps.
A 10 Gage wire will carry 30 amps. But if you are talking 10 Gage fusible link wire then that's different, a fusible link wire is a delayed fuse & will melt if over loaded. The general rule of thumb in the automotive trade is use a fusible link wire 2 Gage smaller then the load wire. If you are using a 10 Gage wire then you should protect the circuit with 14 Gage fusible link. I hope this helps!
6 AWG wire
20 Amp
in air it will be 665Amps.
Sure. You can hook this up to any vehicle. It is easy to do. Just make sure you have the proper gage wire for the amp as a small gage wire can heat up. Also with a smaller gage wire you will lose some power to the amp.
Use 8 gauge wire.
Use 15 amp breaker with 14 gage wire or 20 amp breaker with 12 gage wire. Either way will work just fine.
for residential use 2/0 copper or 4/0 aluminum, if your talking long distances then you need to up size for voltage drop
For safety, approximately 6 or 8 mm. A #14 AWG copper wire with an insulation factor of 90 degree C will have a capacity of 15 amps.
Yes, a 20 amp breaker requires AWG # 12 copper wire. A 15 amp breaker requires AWG # 14 copper wire.
Not a good idea. The 15 amp fuse will be protection a #14 wire which is rated for 15 amps maximum capacity. By changing the 15 amp fuse to a 30 amp fuse you would then be allowing 30 amps maximum capacity on a #14 wire. By doubling the load the extra heat generated on the smaller wire could be enough to melt the insulation from the wire and that could cause the wire to short out. If the wire shorts out inside the wall it means the removal of the wall board to replace the wire to restore the circuit to an operational condition. The proper wire sizing for a 30 amp fuse is, #10 copper wire with an insulation rating of 90 degrees C.
AWG # 8 copper.
A #8 copper conductor with an insulation factor of 75 or 90 degrees C are both rated at 45 amps.
Typical residential electric dryers are on 30 amp circuits, which means 10 gage copper wire. The circuit breaker should match the dryer cord rating, generally 30 amps.