Best Answer

No, you would need 2/0 (2 ought) in copper.

In the US, 2/0 copper is allowed only in residential installations. Otherwise, 3/0 copper is required to a 200 amp service panel.

The electric utility can use whatever they wish. They have their own standards and the NEC does not apply to them.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can you use one ought copper wire size for common lead to a 200 amp service panel?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What size service conductors do you need for a single phase 600 amp commercial panel?

The size of wire for service entrance conductors for a 400 amp 3 phase service could be 500 MCM copper. This is very large size wire and difficult to bend and shape, to connect to terminals in the main disconnect and distribution panel. This problem is solved by using parallel conductors or on higher ampacities triple conductors. Using parallel conductors the wire size would be three ought (3/0) copper.


Ground wire size for 200?

A 200 amp service panel will require a # 4 bare copper ground wire.


Can i use aluminum wire from service panel to hot tub sub panel?

Aluminium wire has produced problems due to unequal expansion/contraction at the brass or copper terminals and long-term surface oxidation. For that reason copper is recommended and there is usually no good reason not to use copper (of the correct gauge for the current).


Can you switch out your 100 amp breaker to a 200 amp one for a service upgrade if your supply wires are already 2-0 copper that is can I keep my existing panel since I have all the space I need?

I doubt if you can fit a 200 amp breaker into a 100 amp panel and it is illegal as the bus bars in a 100 amp panel are rated at 100 not 200 amps. The panel must be of the same capacity in amps as the main breaker that is installed in it. You can go smaller but not larger. The other problem is that a 200 amp service required three ought (000) wire. 000 copper wire with an insulation factor 90 degrees C is rated at 210 amps. Two ought (00) copper wire with an insulation factor of 60C is rated at 145 amps, 75C is rated at 175 amps and 90C is rated at 185 amps. Buy a complete house package that has the main breaker and all of the appliance breakers plus a few breakers for 15 amp circuits, all for one price that is cheaper that buying individual pieces.


What size wire is needed from your meter to your breaker box which is 120 feet away for 200 amp service?

This is a voltage drop question. A voltage value needs to be stated. Assuming that the 200 amp panel is a single phase 120/240 volt sub panel. A #1 copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 200 feet on a 240 volt system.

Related questions

What is the minimum service size for a 225amp residential service?

A 200 amp service panel with a 60 amp sub-panel.


Is number 3 copper ground conductor a common conductor size?

Answer for USA, Canada and countries running a 60 Hertz supply service.CEC states that a #3 bare copper conductor is a common grounding conductor size for a 200 amp service panel and it is the minium size for service raceway and service equipment of 400 amps.


What are service panel bus bars?

Typically copper conductors that provide a phase of electricity.


What size ground wire needed for a 200amp service panel in new jersey?

#6 bare copper wire.


What size neutral wire for 200 amp service panel?

AWG # 3/0 copper.


What size service conductors do you need for a single phase 600 amp commercial panel?

The size of wire for service entrance conductors for a 400 amp 3 phase service could be 500 MCM copper. This is very large size wire and difficult to bend and shape, to connect to terminals in the main disconnect and distribution panel. This problem is solved by using parallel conductors or on higher ampacities triple conductors. Using parallel conductors the wire size would be three ought (3/0) copper.


How decide Electrical Main Feeder size?

It is based on the amperage of the service panel in a single phase home panel useing copper wire use. 100 amp use AWG # 3 copper 200 amp use AWG # 3/0 copper


Ground wire size for 200?

A 200 amp service panel will require a # 4 bare copper ground wire.


Can i use aluminum wire from service panel to hot tub sub panel?

Aluminium wire has produced problems due to unequal expansion/contraction at the brass or copper terminals and long-term surface oxidation. For that reason copper is recommended and there is usually no good reason not to use copper (of the correct gauge for the current).


What wire size for 125 amp service?

The short answer, if using copper, is 0 AWG, commonly referred to as 1/0 or "one ought". Type of wire depends on location & temperature, but in my common scenario I am using 1/0 THHN inside a 2" schedule 40 PVC conduit (3 - 1/0 wires plus a 4 ga bare ground) to run indoors, a distance of about 25 feet from my main panel to a sub for upstairs. I could go into more detail regarding outdoor, direct burial, grounding, aluminum wire, etc but would need more details.


Can you switch out your 100 amp breaker to a 200 amp one for a service upgrade if your supply wires are already 2-0 copper that is can I keep my existing panel since I have all the space I need?

I doubt if you can fit a 200 amp breaker into a 100 amp panel and it is illegal as the bus bars in a 100 amp panel are rated at 100 not 200 amps. The panel must be of the same capacity in amps as the main breaker that is installed in it. You can go smaller but not larger. The other problem is that a 200 amp service required three ought (000) wire. 000 copper wire with an insulation factor 90 degrees C is rated at 210 amps. Two ought (00) copper wire with an insulation factor of 60C is rated at 145 amps, 75C is rated at 175 amps and 90C is rated at 185 amps. Buy a complete house package that has the main breaker and all of the appliance breakers plus a few breakers for 15 amp circuits, all for one price that is cheaper that buying individual pieces.


What size underground service entry cable needed for 100 amp sub panel 600 feet from main?

AWG 2/0 copper.