Want this question answered?
Receptacles are not wired in series. Receptacles are actually wired in parallel, what this means is that all phase wires (black) in a receptacle's box should terminate to the brass screws on each device, and all neutral (white) wires in the box should terminate on the silver screws on each device.
If you are referring to house wiring then the answer is no. A breaker protects the wire size that is connected to the breaker. In home wiring most homes are wired with a #14 wire which is rated at 15 amps. That is why the wire is protected by a 15 amp breaker. The correct wire size to connect to a 40 amp breaker is a #8. This size wire is too large to connect to receptacles an light fixture terminals.
code states that if a water source such as a sink is within 6 feet of a receptacle, that recetacle (s), must be protected by a GFCI receptacle. I believe the actual distance is 5 feet. Please forgive me if I'm wrong. But the NEC also requires that ANY counter top receptacles in a kitchen and receptacles ANYWHERE in a bathroom must be GFCI protected. More directly to your question, ordinary receptacles can be protected from a GFCI receptacle if properly wired. They are designed to do that. It is a way to save money. You may also consider a GFCI breaker if you have many receptacles to protect. I was told once that there is a limit of 3 "piggy backed" receptacles per GFCI but I have never seen that in the NEC.
No, not in the North American electrical system. Opening up a neutral on a three wire circuit could create a series circuit if two devices are plugged into the same receptacle. This is how kitchen counter receptacles are wired in all new homes.
Wall receptacles are wired in parallel. black to black, white to white, ground to ground.
The receptacles will be wired in parallel with each other.
Receptacles are not wired in series. Receptacles are actually wired in parallel, what this means is that all phase wires (black) in a receptacle's box should terminate to the brass screws on each device, and all neutral (white) wires in the box should terminate on the silver screws on each device.
Improperly wired receptacle is the normal cause.
Wired
It protects the insulated conductors against mechanical and environmental damage.
Yes, but my advice to you is don't use that method to terminate the receptacle just because it is there. The internal connection is just a spring tension holding the wire against a flat surface. That isas tight as the connection can become.Take a bit more time and use the screw terminal. Make a hook in the wire and place it around the screw the same way as the screw turns in. This way the screw tightens the hook around the screw and the termination is the best that you an get.Remember loose connections cause heat when under load and heat will cause premature failure of the device connected. Might as well do it right the first time.
NO! You are drastically in excess of electrical code requirement. A 15 amp circuit should not exceed eight total receptacles and/or lighting devices.
If you are referring to house wiring then the answer is no. A breaker protects the wire size that is connected to the breaker. In home wiring most homes are wired with a #14 wire which is rated at 15 amps. That is why the wire is protected by a 15 amp breaker. The correct wire size to connect to a 40 amp breaker is a #8. This size wire is too large to connect to receptacles an light fixture terminals.
Possibility #1 Plugging in a high consumption appliance. Possibility #2 Loose connection. Look for glazing, or discoloration on the prongs of the device. Old receptacles can lose tension in the female spring loaded contacts. Check to see if the receptacle is Back wired through a hole in the back, or if the wires are terminated on the side screws. Back wired receptacles use the same spring-loaded contacts on the wire connection. Any loose connection can cause excessive resistance resulting in higher amperage and heat.
A Voltage Regulator is just a Zener Diode that is wired across the alternator terminals. ... no. Doing this will blow the zener - don't try it at home or anywhere else.
A Voltage Regulator is just a Zener Diode that is wired across the alternator terminals. ... no. Doing this will blow the zener - don't try it at home or anywhere else.
code states that if a water source such as a sink is within 6 feet of a receptacle, that recetacle (s), must be protected by a GFCI receptacle. I believe the actual distance is 5 feet. Please forgive me if I'm wrong. But the NEC also requires that ANY counter top receptacles in a kitchen and receptacles ANYWHERE in a bathroom must be GFCI protected. More directly to your question, ordinary receptacles can be protected from a GFCI receptacle if properly wired. They are designed to do that. It is a way to save money. You may also consider a GFCI breaker if you have many receptacles to protect. I was told once that there is a limit of 3 "piggy backed" receptacles per GFCI but I have never seen that in the NEC.