No. This practice is a violation of Article 210.19 (A) of the NEC. "Conductors of branch circuits supplying more than one receptacle for cord-and-plug-connected portable loads shall have an ampacity of not less than the rating of the branch circuit."

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: DoesCode permit connecting receptacles to a 20ampere branch circuit using short lengths of 14AWG conductors as the pigtail between the receptacle terminals and the 12AWG branch-circuit conductors?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

What are skirted receptacles?

A commercial receptacle that is used to prevent arching.


Can you feed multiple outlets to one GFCI outlet near the sink?

code states that if a water source such as a sink is within 6 feet of a receptacle, that recetacle (s), must be protected by a GFCI receptacle. I believe the actual distance is 5 feet. Please forgive me if I'm wrong. But the NEC also requires that ANY counter top receptacles in a kitchen and receptacles ANYWHERE in a bathroom must be GFCI protected. More directly to your question, ordinary receptacles can be protected from a GFCI receptacle if properly wired. They are designed to do that. It is a way to save money. You may also consider a GFCI breaker if you have many receptacles to protect. I was told once that there is a limit of 3 "piggy backed" receptacles per GFCI but I have never seen that in the NEC.


How do you install multiple GFCI receptacles?

A GFCI receptacle can extend its protection to regular receptacles connected to the output side of the GFCI. Each actual GFCI receptacle should be directly connected to a breaker in electric panel.


How do you wire receptacles in series?

Receptacles are not wired in series. Receptacles are actually wired in parallel, what this means is that all phase wires (black) in a receptacle's box should terminate to the brass screws on each device, and all neutral (white) wires in the box should terminate on the silver screws on each device.


Can reverse polarity burn a tv set?

If, by 'reverse polarity', you mean the accidental reversal of the line and neutral conductors at the socket outlet or receptacle, then the answer is no.

Related questions

WHAT IS THE FUNCTION OF RECEPTACLE?

The function of the seminal receptacles is to receive semen.


What are skirted receptacles?

A commercial receptacle that is used to prevent arching.


Where can one find more information on receptacles?

Information on receptacles can be found on the websites of companies that sell receptacles. For example, if the receptacle one has in mind is a waste paper bin, visit Amazon and find a waste paper bin for sale. Then one will find information about that receptacle, for example.


What is the reference to female when explaining electrical receptacles?

No. The term female receptacle means there is a hole and a male receptacle means it has a pin sticking out.


What is the function of receptacles of a flower?

The Receptacle of a flower is the bottom of the flower. It holds everything together. reproductive parts of a plant. Receptacle is female


What causes reversed polarity in a 110 volt receptacles?

Improperly wired receptacle is the normal cause.


What might happen if the line and load connetions of a feedthrough gfci receptacle were reversed?

Most probably the receptacles downstream from the GFCI would not be protected by the GFCI receptacle.


What would cause screws on receptacle to become red hot?

There are three major causes of hot screws on a receptacle. 1.. Overcurrent: Receptacles are usually rated at 15 amps, occasionally 20 amps. If the circuit breaker feeding it is too large or faulty, the receptacle could overheat due to the loads it is feeding. 2.. Loose screws at the receptacle. This condition leads to arcing at the receptacle and evetually, fire. 3.. Copper contamination. Carbonization or crystalization can occur on the conductors at the screw terminal. This can usually be cleaned up with emery cloth.


Where must GFCI receptacles be installed in residential garages?

All receptacles in a garage must be GFCI protected by code. Typically, the first receptacle in the circuit (location is irrelevant) must be a GFCI, then all others down stream in the circuit will be protected, and can be common receptacles.


What are the two basic specifications that electrical receptacles are based on?

One basic specification that electrical receptacles are based on is the amount of amperage that the receptacle can legally handle. The other basic specification is the amount of voltage that the receptacle can legally handle. This is the reason that there are so many different types to choose from. When buying a receptacle you should be armed with the knowledge of what the voltage is going to be and what the load amperage is going to be to get the proper receptacle. Each receptacle has different pin configurations for voltage and amperage. This is a safety factor so that inter changeability can not happen.


What is the ampere specification of switches and sockets used in house wiring?

In North America the standard receptacles and switches are rated at 15 amps. A dryer receptacle is rated at 30 amps and a range receptacle is rated at 50 amps. New code rules are allowing 20 receptacles in some specific locations.


What is the proper height to mount a receptacle in a basement in Canada building code?

The is no height stated in the CEC as to height of receptacles. If the basement walls are studded out, then install the receptacles at the normal 300 mm above the floor.