No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
Not that I know of. The largest GFCI breaker I have seen is a 60 amp.
Yes.Additional InformationBreakers and fuses protect the wires to prevent fire. The 100 Amp breaker in the meter base (main) protects the wire from the meter base to the breaker panel. The 50 Amp breaker in the breaker panel protects the wire from the breaker panel to the outlet. Sometimes the 100 amp main breaker is located in the panel.If you are asking "Can you use two 50 amp breakers for the main breakers with a 100 amp service, then yes you can. The National Electrical Code allows you to use up to 6 breakers as the main overcurrent protection.
No tandem breakers are of the same value.
If a 100 amp breaker keeps tripping there is an overload on the system.
If the 12,000 BTU A/C only requires 20 amps to run then yes you can use the same 12 gauge wire but you cannot change it to a 15 amp breaker. You will need to install a 20 amp double pole breaker. If it requires more than 20 amps you will have to replace the wiring and breaker.
Not that I know of. The largest GFCI breaker I have seen is a 60 amp.
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
A 100-A sub-panel would be fed from a 100-A breaker.
Yes.Additional InformationBreakers and fuses protect the wires to prevent fire. The 100 Amp breaker in the meter base (main) protects the wire from the meter base to the breaker panel. The 50 Amp breaker in the breaker panel protects the wire from the breaker panel to the outlet. Sometimes the 100 amp main breaker is located in the panel.If you are asking "Can you use two 50 amp breakers for the main breakers with a 100 amp service, then yes you can. The National Electrical Code allows you to use up to 6 breakers as the main overcurrent protection.
probally about 100 dollars
No tandem breakers are of the same value.
If a 100 amp breaker keeps tripping there is an overload on the system.
Yes, but they obviously cannot be simultaneously loaded their maximum loads because the 400-amp breaker will blow well before that. Similarly, you can have multiple 100-amp panels fed from a 200-Amp main breaker, knowing that you will NEVER have 100 amps running in all panels at the same time.
50 amp breaker wired with AWG # 6 wire.
If the 12,000 BTU A/C only requires 20 amps to run then yes you can use the same 12 gauge wire but you cannot change it to a 15 amp breaker. You will need to install a 20 amp double pole breaker. If it requires more than 20 amps you will have to replace the wiring and breaker.
50 amp breaker.
can a 20 amp double pole circuit breaker be used for 2 different 120 v circuits using 14 - 2 wire