Remove the 30 amp double pole breaker and install at least one single pole 15 amp breaker. It is best if the other slot is not left open so if you have another single pole breaker of any size install it in the 2nd spot so it isn't open when you replace the cover on the panel.
For your 15 amp circuit you need #14 gauge copper wire or larger with a hot, neutral, and ground. Your 30 amp circuit was probably wired with #10 gauge conductors. These will probably work on your 15 amp circuit but it may be difficult to connect #10 conductors to devices.
You cannot wire a normal 120V outlet directly from a double pole circuit breaker as it is designed for higher voltage applications. You would need to install a single pole circuit breaker for a 120V outlet.
For a 120V hand dryer with a rating of 20 amps, use a 20 amp breaker to match the device's ampacity and prevent potential overloading or overheating issues.
No the outlet holes are in parallel so the total ampacity of the receptacle is still 15 amps.
No, it is not safe to use a double pole 15 amp breaker in place of a 20 amp single pole breaker for a 12000 BTU air conditioner. The breaker size must match the electrical requirements of the appliance to prevent overheating and potential fire hazards. It is recommended to consult with a qualified electrician to ensure the proper breaker is used.
Yes, a double pole 20 amp breaker can be used with 12-2 wire for a 240V circuit. However, make sure the device you are connecting requires 240V and not 120V. Also, consult local electrical codes and regulations to ensure compliance with safety standards.
You cannot wire a normal 120V outlet directly from a double pole circuit breaker as it is designed for higher voltage applications. You would need to install a single pole circuit breaker for a 120V outlet.
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
For a 120V hand dryer with a rating of 20 amps, use a 20 amp breaker to match the device's ampacity and prevent potential overloading or overheating issues.
No the outlet holes are in parallel so the total ampacity of the receptacle is still 15 amps.
No, it is not safe to use a double pole 15 amp breaker in place of a 20 amp single pole breaker for a 12000 BTU air conditioner. The breaker size must match the electrical requirements of the appliance to prevent overheating and potential fire hazards. It is recommended to consult with a qualified electrician to ensure the proper breaker is used.
can a 20 amp double pole circuit breaker be used for 2 different 120 v circuits using 14 - 2 wire
Yes, a double pole 20 amp breaker can be used with 12-2 wire for a 240V circuit. However, make sure the device you are connecting requires 240V and not 120V. Also, consult local electrical codes and regulations to ensure compliance with safety standards.
No, it is not recommended to downgrade a 240V 50A circuit to a 120V 30A circuit. The wiring and breaker size must match the voltage and amperage requirements of the appliances being used. It is important to consult with a licensed electrician for any modifications to ensure safety and compliance with electrical codes.
no. depending on length of run you'll need either 10 or 6 gauge wire for a 30 amp double pole breaker.
No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
No, the wire will overheat.
You would need one 30 amp double-pole breaker in the breaker box for a 240V cooktop.