No. Usually when you get to that size panels the grounds are stranded.
No, you can use #4 bare copper ground wire.
Yes, there are ground wire gauges. The approiate size ground wire must be matched to the size service you are installing. For instance a 200 amp serivce must be grounded with a # 4 bare copper ground wire.
NEC code requires #6 bare copper.
A 200 amp service using a uffer ground will need a #3 bare copper wire. The bare copper wire is to be not less than 20 feet in length. It also has to be within 2" of the concrete foundation footing that is in direct contact with the earth. The depth can not be less than 2 feet below finished grade.
As a service entrance wire you need AWG # 3/0 gauge copper.
A 200 amp service panel will require a # 4 bare copper ground wire.
No, you can use #4 bare copper ground wire.
On a 200 amp or any size service the ground wire is easily identified. Look in the distribution panel for the neutral bus bar. This is where the service neutral (white wire) is connected to the distribution panel. There you will see a bare copper wire connected to the same neutral bar. This is the ground wire that is connected to the ground rods out side of the house.
Yes, there are ground wire gauges. The approiate size ground wire must be matched to the size service you are installing. For instance a 200 amp serivce must be grounded with a # 4 bare copper ground wire.
Not looped but connected to both ground rods and then connected to the meter base.
It is very likely that the 120A current you quote is the output current. Check your Welder Box and look at the input current. It is likely around 30 Amps. To wire a 30A circuit you will need 10 gauge wire and it is likely 3 conductots + ground. You will need a 230V Breaker. Connect the black and red wires from the 10 gauge cable to the breaker, white wire to neutral and ground to ground.
A typical all-electric home built in Florida in 1992 may have a total household amperage of 150-200 amps. This is sufficient to support the electrical needs of the home's appliances and devices. It's always recommended to consult a licensed electrician to assess the specific requirements of the home.
You do not use a ground wire in the connection from the meter base to the distribution panel. A bonding wire may be required if the service is using PVC conduit.
Stranded wire is the choice as you have tight bends and a short run, solid wire isn't very good in this format.
A 000 copper wire with an insulation factor of 90 degrees C is rated at 210 amps. You will need three of these wires. Two hots and a neutral. You will also need a separate ground wire that runs to an outside ground rod. See your local building requirements for more information regarding those specifications.
NEC code requires #6 bare copper.
200 amp service in chicago uses 3 aught.