The type of wire does not generally determine whether something is a ground wire or not. A wire is a ground wire if it is connected to the ground of a circuit, or the common ground (the reference point of a circuit that is at 0 volts).
However, in relation to the grounding rod used to connect the main circuit panel for a house, the rods are almost always made of steel that are copper plated.
The wire sheathing itself is usually marked. e.g. 14 CU 2 or 14/2 CU will indicate 14 gauge 2-wire (+ ground) copper (CU being the symbol for copper on the periodic table). For 15amp circuits you will likely has 14 gauge wire with most of that being 14/2 (Usually white, black, and bare copper).
On a 30 amp circuit, you would use a #10 copper ground. The ground never has to be larger than the ungrounded conductors.
If the copper wire really is pure copper then the only element in the copper wire is copper (Cu).
Ground wire to neutral wire.
the green wire its ground so you have black withe an ground
The wire sheathing itself is usually marked. e.g. 14 CU 2 or 14/2 CU will indicate 14 gauge 2-wire (+ ground) copper (CU being the symbol for copper on the periodic table). For 15amp circuits you will likely has 14 gauge wire with most of that being 14/2 (Usually white, black, and bare copper).
On a 30 amp circuit, you would use a #10 copper ground. The ground never has to be larger than the ungrounded conductors.
Foe a copper wire the symbol is Cu.
It means a wire in the ground.
That Thermostat is LOW voltage. IT does not have a ground wire. There is no need for a ground. it only opperates on 24 volts. there may be a green wire but it does not mean it is a ground
If there is no ground wire connect the ground wire to the neutral wire.
as a cu wire is a conductor, electrical current does go through it, but some of the electrical energy gets converted into heat energy, and that is why the wire aslo heats up a bit.
Check the continuity of the ground wire from both the ends. Ensure the ground wire is properly connected to earth / ground terminals
If you are connecting 120 volts, you connect the black wire to the breaker, white wire to the neutral bar, and ground wire to the ground bar. If you are connecting 240 volts connect the black & white wires to the breaker, & ground wire to the ground bar.
Yes, if there in no ground wire that is acceptable on a home with no ground wires.
If the voltage between real ground and the ground wire is not 0.0000 Volt, then the wire is not grounded properly.
There is NO reaction. FeSO4 + Cu --> (nothing) (The opposite reaction works well: Iron wire in copper sulfate) (CuSO4 + Fe --> FeSO4 + Cu)