Anything that does not pull over 50 amps.
If you are asking, can three separate 240 volt circuits be run off of one 50 amp breaker then the answer is no. Not without knowing what the loading of the three circuits are and whether all three circuits could be on at the same time.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.
Not legally because the rating of the 30 amp receptacle would have a 50 amp breaker ahead of it. If you reduced the feed breaker to 30 amps and still use the #6 wire, this would be within the electrical code rules.
50 watt equals less than 1/2 amp current flow at 120 volts so you can have 30 light on a 15amp breaker or 40 on a twenty amp breaker.
If you are asking, can three separate 240 volt circuits be run off of one 50 amp breaker then the answer is no. Not without knowing what the loading of the three circuits are and whether all three circuits could be on at the same time.
50 amp breaker.
A 50 amp breaker is an overcurent device.
No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.
Not legally because the rating of the 30 amp receptacle would have a 50 amp breaker ahead of it. If you reduced the feed breaker to 30 amps and still use the #6 wire, this would be within the electrical code rules.
No, because if you switch a 50-amp load on, it will blow a 40-amp circuit breaker if the load exceeds 40 amps, which is likely.
No there are no adapters made for these types of installations. The reason there are no adapters is to provide a factor of safety. To plug a 30 amp plug into a 50 amp receptacle could allow 50 amps to be applied to a 30 amp rated cord. The 50 amp receptacle is more than likely being fed by a 40 amp breaker. Just change the plug cord to match the ampacity of the breaker ahead of the 50 amp receptacle. Or change the 50 amp receptacle and 40 amp breaker to a 30 amp breaker and use your existing cord plug.
Yes.Additional InformationBreakers and fuses protect the wires to prevent fire. The 100 Amp breaker in the meter base (main) protects the wire from the meter base to the breaker panel. The 50 Amp breaker in the breaker panel protects the wire from the breaker panel to the outlet. Sometimes the 100 amp main breaker is located in the panel.If you are asking "Can you use two 50 amp breakers for the main breakers with a 100 amp service, then yes you can. The National Electrical Code allows you to use up to 6 breakers as the main overcurrent protection.
6ga should be used. It might not be against codes where you are,and you might have a 50amp installed for something that only uses 40amp, but it should be done right, and 6ga should be used off of a 50amp breaker.
No, the 50 amp breaker should not be getting hot with a 17 amp load. Shut the service off at the disconnect and check the bolts that tighten the breaker to the distribution's bus bars. Check the tightness of the load side of the breaker. if all of these connections are tight then change the breaker out for a new one.