If you are asking, can three separate 240 volt circuits be run off of one 50 amp breaker then the answer is no. Not without knowing what the loading of the three circuits are and whether all three circuits could be on at the same time.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.
Not legally because the rating of the 30 amp receptacle would have a 50 amp breaker ahead of it. If you reduced the feed breaker to 30 amps and still use the #6 wire, this would be within the electrical code rules.
50 watt equals less than 1/2 amp current flow at 120 volts so you can have 30 light on a 15amp breaker or 40 on a twenty amp breaker.
If you are asking, can three separate 240 volt circuits be run off of one 50 amp breaker then the answer is no. Not without knowing what the loading of the three circuits are and whether all three circuits could be on at the same time.
A 50 amp breaker is an overcurent device.
No, you should not run 8 gauge wire on a 50 amp breaker. The wire size should be compatible with the amperage rating of the breaker to ensure safety and prevent overheating. For a 50 amp breaker, you should use a minimum of 6 gauge wire.
No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.
Not legally because the rating of the 30 amp receptacle would have a 50 amp breaker ahead of it. If you reduced the feed breaker to 30 amps and still use the #6 wire, this would be within the electrical code rules.
No, because if you switch a 50-amp load on, it will blow a 40-amp circuit breaker if the load exceeds 40 amps, which is likely.
For a 41 amp load, you would typically use a 50 amp circuit breaker. The general rule is to select a breaker size that is 125% of the continuous load amps or equal to the load amps if it is not a continuous load. In this case, 41 amps is considered a continuous load, so you would round up to the nearest available breaker size, which is 50 amps.
Yes, a 100 amp main panel can have 2 separate 50 amp circuits protected by 50 amp breakers. This configuration allows for two separate circuits drawing up to 50 amps each from the main panel without overloading the panel's 100 amp capacity.
No, the 50 amp breaker should not be getting hot with a 17 amp load. Shut the service off at the disconnect and check the bolts that tighten the breaker to the distribution's bus bars. Check the tightness of the load side of the breaker. if all of these connections are tight then change the breaker out for a new one.
Not if it's functioning properly. The purpose of a circuit breaker is to shut off power if the circuit exceeds the rated power capacity of the wires. Don't plan to exceed the 30 Amp capacity of your house wiring; the results will be destructive.