It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
The 20A breaker can handle (25%) more power than the 15A breaker, because of this the wires used inside the walls is larger. Some circuits must be 20A, the laundry and kitchen are examples of 20A circuits.
Does it surge past 120?? Drops are due too the fact that there are too many outlets or devices on one line. Trace the line that you have a voltage drop in and find which breaker it is, if the line that comes off the breaker is a 12 gauge wire and the breaker is a 15amp breaker you can put in a 20amp breaker. If the line is a 14 gauge line then you must leave the 15amp breaker in place and remove a device from it.
The minimum size wire a 20 amp breaker needs to be connected to is a #12 wire. The 15 is probably connected to a #14 right now which is only rated for 15 amps. Remember the breaker is sized to the wires ampacity not the load .
Your only hope is that someone wired the box not to code and that there are two wires going into the offending breaker. If you can't separate wires you can't distribute the load.
is it polesible to run a range of appliances on a single 15amp receptical
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
The 20A breaker can handle (25%) more power than the 15A breaker, because of this the wires used inside the walls is larger. Some circuits must be 20A, the laundry and kitchen are examples of 20A circuits.
Does it surge past 120?? Drops are due too the fact that there are too many outlets or devices on one line. Trace the line that you have a voltage drop in and find which breaker it is, if the line that comes off the breaker is a 12 gauge wire and the breaker is a 15amp breaker you can put in a 20amp breaker. If the line is a 14 gauge line then you must leave the 15amp breaker in place and remove a device from it.
The minimum size wire a 20 amp breaker needs to be connected to is a #12 wire. The 15 is probably connected to a #14 right now which is only rated for 15 amps. Remember the breaker is sized to the wires ampacity not the load .
If the circuit breaker is in the off position there is no need of overload protection. Overload protection monitors the load amperage, If there is no amperage through the circuit there is nothing to monitor.
Your only hope is that someone wired the box not to code and that there are two wires going into the offending breaker. If you can't separate wires you can't distribute the load.
50 watt equals less than 1/2 amp current flow at 120 volts so you can have 30 light on a 15amp breaker or 40 on a twenty amp breaker.
A 20 amp circuit with #12 gauge wire will work in any event but if the nameplate recommends a 15 amp circuit then #14 gauge wire on a 15 amp circuit is sufficient. In either case you will have a double pole breaker and your equipment may not require a neutral. Always run a grounding conductor.
Consider a case , where an earth switch is closed and You are trying to close the Line breaker , in this situation , the relay trips the breaker instantaneously without any conditions or any time delay . This is called Switc On To Fault .
Technically, they can be on a 15 amp breaker when you use 15 amp outlets. There is a difference. Be sure to check your local code (just call the city building department and tell them you have a code question). some cities require the bedroom outlets to be on an arc-fault breaker.