Yes, a #12 AWG conductor has a greater diameter than a #14 AWG conductor. A #12 conductor has an ampacity of 20 amps whereas a #14 conductor only has an ampacity of 15 amps.
It's a table that shows the ampacity ratings for the particular wire size and insulation you are using. Example: #12 THHN CU is rated @ 30amps under the 90 degree column. (#12)is the wire size, (THHN)is the type of insulation on the wire (CU)is copper. You shouldn't be using the chart unless you're a qualified electrician simply because there are many sub rules and exceptions.
Isn't it 35, according to the NEC 310.15(B)(16) Table.
It will taken 8 amps <<>> The conversion of 2.5 sq mm wire to AWG is equal to a #12 wire. The ampacity of a #12 copper wire with an insulation factor of 90 degrees C is 20 amps.
School question. The answer can be found in your electrical code book.
Yes, a #12 AWG conductor has a greater diameter than a #14 AWG conductor. A #12 conductor has an ampacity of 20 amps whereas a #14 conductor only has an ampacity of 15 amps.
It's 12 AWG THHN, 1/2" PVC would be just fine
Yes the ampacity of #12 is 20 amps whereas the ampacity of #14 is 15 amps, so you are well within the range using #12 wire.
According to appendix C of the NEC, 3 #2 awg are permitted in a 1" EMT.
12 AWG should be fine since resistance of wire is only about .16 ohms per 100 ft.
It's a table that shows the ampacity ratings for the particular wire size and insulation you are using. Example: #12 THHN CU is rated @ 30amps under the 90 degree column. (#12)is the wire size, (THHN)is the type of insulation on the wire (CU)is copper. You shouldn't be using the chart unless you're a qualified electrician simply because there are many sub rules and exceptions.
"... the rating of the overcurrent device shall not be less than the non-continuous load plus 125% of the continuous load." NEC 2008 Article 210.20(A) Furthermore, the ampacity of the conductor must be derated to 80% of allowable ampacity as stated in Table 310.16. Please take note of the exception to the table for #14 AWG, #12 AWG, and #10 AWG in Article 240.4(D) which automatically derates small conductors such as these to 15A, 20A, and 30A respectively. Also be aware of all other ampacity derating that may be required by Article 310 and Article 422.
1/0 copper thhn covering. 3/0 aluminum again thhn covering
Isn't it 35, according to the NEC 310.15(B)(16) Table.
12 awg is larger.
What is the final ampacity for a number 12 NM-B conductor? Answer this question…
It will taken 8 amps <<>> The conversion of 2.5 sq mm wire to AWG is equal to a #12 wire. The ampacity of a #12 copper wire with an insulation factor of 90 degrees C is 20 amps.