EMT is electrical metallic tubing. In the electrical trade there are nominal sizes expressed as a standard size. To answer your question you must state the conduit size in either electrical terms or in standard size terms to get a conversion size.

For example standard size 1/2" EMT has an actual diameter size of 3/4" and the 1/2"EMT connector for the 1/2" EMT conduit needs a 7/8" hole.


Likewise with 3/4" EMT the actual outside diameter is 15/16" and the 3/4" EMT connector needs a 1-1/8" hole.

User Avatar

Wiki User

9y ago

What else can I help you with?

Related Questions

What is the hole size required for a 2.5 conduit?

A trade size hole for a 2-1/2" EMT conduit connector, the hole needs to be 2-7/8" in diameter. A 3" rigid conduit can also use this size hole without the lock nuts falling into the hole.


Can 480 volt electric be run in emt conduit?

Yes 480 volt electric wiring can be run in emt conduit.


What is the multiplier for 45 degree offset in conduit bending?

Back set for all conduit sizes is not the same. The greater the diameter of the conduit the length of back set increases. Without the diameter size of the conduit, an answer can not be given.


What is the recommended conduit size for a 200 amp service?

The recommended conduit size for a 200 amp service is typically 2 inches in diameter.


How many number 12 THHN conductors are allowed in half inch EMT?

According to the 2005 NEC Annex C, table C.1 you are allowed nine #12 THHN conductors in a 1/2" trade size EMT conduit. If your conduit run is any length at all, you would be wise to increase the conduit size to 3/4". as pulling 9 #12's for any length in 1/2" EMT is very difficult.


What is the smallest size emt conduit that can be used with nineteen 10 gauge thwn wires?

1 1/2 inch


What is the appropriate conduit size for accommodating 6/3 wire?

The appropriate conduit size for accommodating 6/3 wire is typically 1 inch in diameter.


What is the recommended conduit size for accommodating 6/3 wire?

The recommended conduit size for accommodating 6/3 wire is typically 1 inch in diameter.


How many wires can you put in a conduit?

Depends on the size of the conduit and the size of the wire.Allowable Conduit Fill CapacitiesSize and Type Of Conduit #14 Wire #12 Wire #10 Wire 1/2" EMT 12 9 5 3/4" EMT 22 16 10 1" EMT 35 26 16 1 1/2" EMT 84 61 38 1/2" PVC 10 7 4 3/4" PVC 18 13 8 1" PVC 32 23 15 1 1/2" PVC 80 58 36


What are the differences between IMC and EMT conduit and how do they compare in terms of their applications and benefits?

IMC conduit is thicker and heavier than EMT conduit, making it more durable and suitable for outdoor and industrial applications. IMC conduit is also more resistant to damage and corrosion. EMT conduit, on the other hand, is lighter and easier to bend, making it ideal for indoor and residential applications where flexibility is needed. In terms of benefits, IMC conduit provides better protection for wires and cables, while EMT conduit is more cost-effective and easier to install.


When exist a junction box EMT conduit must be supported with how many inches?

When exist a junction box EMT, conduit must be supported within 18 inches.


What are the differences between EMT and PVC conduit, and which one is more suitable for my electrical wiring project?

EMT conduit is made of metal and is more rigid, while PVC conduit is made of plastic and is more flexible. EMT conduit is typically used for indoor applications, while PVC conduit is better suited for outdoor or underground installations. The choice between the two depends on the specific needs of your electrical wiring project.