answersLogoWhite

0


Best Answer

Depends on the size of the conduit and the size of the wire.

Allowable Conduit Fill CapacitiesSize and Type Of Conduit #14 Wire #12 Wire #10 Wire 1/2" EMT 12 9 5 3/4" EMT 22 16 10 1" EMT 35 26 16 1 1/2" EMT 84 61 38 1/2" PVC 10 7 4 3/4" PVC 18 13 8 1" PVC 32 23 15 1 1/2" PVC 80 58 36
User Avatar

Wiki User

10y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How many wires can you put in a conduit?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Can you put low voltage sound wires and low voltage light wires in the same conduit?

noyou can not


Can you put two wires in one conduit and two wires in another conduit of the same circuit?

No, each conduit should only contain wires from the same circuit. Mixing circuits in a conduit can lead to interference and safety hazards. It is always best practice to keep conductors of the same circuit together to prevent potential issues.


How many 18AWG wires fit in a 1 conduit?

53


How many number 12 wires can fit in a three quarter inch conduit?

10


Does triplex wire need to be in conduit under a house?

Yes. If they are single wires they need to be in a conduit.


How many 18AWG wires fit in a 2 inch conduit?

Approximately 9-10 18AWG wires can fit in a 2 inch conduit, depending on the type of insulation on the wires and the specific requirements of the installation. It's always advisable to consult the National Electrical Code (NEC) or local regulations for specific guidelines on conduit fill capacity.


Can you use existing PVC conduit run from basement to 8th floor for 120v circuits for chillers?

The simple answer to your question is yes. But there are limits to how many wires can be in any conduit, and the current carrying capacity of the conductors can be affected by distance, ambient temperature, and how many conductors are contained in the same conduit. Other things to consider are, Can you physically fit the wires in there? Would it be easier to run a new conduit? Do you have the manpower necessary to get the work done?


How many number 10 wires can fit in a 1 EMT conduit?

16 current carry conductors


How many number 12 thhn wire can you fit into half inch conduit?

You can fit approximately 9 number 12 THHN wires into a half inch conduit. It's important to follow the National Electrical Code rules for conduit fill to ensure proper installation and safety.


What is the difference between one current carrying conductor in a conduit and a hot and switch leg in a conduit?

In the first part of the question there will be only one wire in the conduit, in the second part of the question there will be two wires in the conduit.


What size conduit is needed for wiring in Indian houses?

The size of conduit is based on the size of the wires in it. The size of the wires depends on the load connected in the house. Without these other two values an answer can not be given.


What is conduit fitting?

Conduit fitting is used on metal pipes that house electrical wires. These fittings are not only to connect the various pieces together, but to keep a relatively water tight seal to the wires.