answersLogoWhite

0


Want this question answered?

Be notified when an answer is posted

Add your answer:

Earn +20 pts
Q: What is the minimum diameter required for pipes or conduit used as grounding electrodes?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Does the Nec allow grounding electrode conductor to be run in conduit that has other conductors in the conduit and what code section?

No, the bare copper grounding conductor can not be in a conduit with other conductors. It can be in conduit by itself to provide mechanical protection for the wire.


Does the metal conduit count as a ground?

No, each conduit must contain a separate grounding conductor.


Are ground wires required in steel or aluminum flex conduits?

Yes, any flexible conduit that has live wires drawn into it must have a ground wire also installed with the "hot" conductors. The reasoning behind this rule is that the flex in the conduit is coiled and has a long length to it. The continuation of the grounding medium through the tightness of the conduit connectors to the flex was not considered a properly secured grounding system so to overcome this weakness in the grounding system, a ground wire now has to be installed.


Is it permitted to use flexible metal conduit over 6 ft in length as a grounding means?

is it permitted to use flexible metal conduit over 6 ft in length as a grounding means


Is it permitted to use flexible conduit over 6 feet in length as a grounding means?

No. The new electrical code change does not allow any flexible conduit to be used as a ground means. It is now required to have a green ground wire pulled into the conduit with the other conductors in the flexible conduit. This grounded bonding conductor is not counted as wire fill when calculating the size of the flexible conduit to use


What is the multiplier for 45 degree offset in conduit bending?

Back set for all conduit sizes is not the same. The greater the diameter of the conduit the length of back set increases. Without the diameter size of the conduit, an answer can not be given.


What is the hole size required for a 2.5 conduit?

A trade size hole for a 2-1/2" EMT conduit connector, the hole needs to be 2-7/8" in diameter. A 3" rigid conduit can also use this size hole without the lock nuts falling into the hole.


Do light fittings need to be earthed?

Normally the fixtures come with a grounding screw that you attach the grounding wire to. If the box you attaching the fixture to is metal and there is no grounding wire present then the grounded conduit should ground you fixture.


Is conduit required for basement electrical outlets?

Conduit is not required for residential electrical IF THE WIRING IS BEHIND THE WALL. If it's exposed wiring, you'll need to use conduit.


What size grounding wire do you use as the 4th wire running in your conduit from your 200 amp meter box to your 200amp service panel this is the ground wire from box to box?

You do not use a ground wire in the connection from the meter base to the distribution panel. A bonding wire may be required if the service is using PVC conduit.


What size drill bit do you need for a piece of conduit?

Depends on the diameter of the conduit. Try for 1/4" larger diameter drill bit.


Is a separate ground wire required for each circuit in a conduit?

Not normally. An elaboration of what circuits are in the conduit and what type of conduit it is would be useful, though, and necessary to give a definitive answer.