Want this question answered?
No, the bare copper grounding conductor can not be in a conduit with other conductors. It can be in conduit by itself to provide mechanical protection for the wire.
No, each conduit must contain a separate grounding conductor.
Yes, any flexible conduit that has live wires drawn into it must have a ground wire also installed with the "hot" conductors. The reasoning behind this rule is that the flex in the conduit is coiled and has a long length to it. The continuation of the grounding medium through the tightness of the conduit connectors to the flex was not considered a properly secured grounding system so to overcome this weakness in the grounding system, a ground wire now has to be installed.
Back set for all conduit sizes is not the same. The greater the diameter of the conduit the length of back set increases. Without the diameter size of the conduit, an answer can not be given.
A trade size hole for a 2-1/2" EMT conduit connector, the hole needs to be 2-7/8" in diameter. A 3" rigid conduit can also use this size hole without the lock nuts falling into the hole.
No, the bare copper grounding conductor can not be in a conduit with other conductors. It can be in conduit by itself to provide mechanical protection for the wire.
No, each conduit must contain a separate grounding conductor.
Yes, any flexible conduit that has live wires drawn into it must have a ground wire also installed with the "hot" conductors. The reasoning behind this rule is that the flex in the conduit is coiled and has a long length to it. The continuation of the grounding medium through the tightness of the conduit connectors to the flex was not considered a properly secured grounding system so to overcome this weakness in the grounding system, a ground wire now has to be installed.
is it permitted to use flexible metal conduit over 6 ft in length as a grounding means
No. The new electrical code change does not allow any flexible conduit to be used as a ground means. It is now required to have a green ground wire pulled into the conduit with the other conductors in the flexible conduit. This grounded bonding conductor is not counted as wire fill when calculating the size of the flexible conduit to use
Back set for all conduit sizes is not the same. The greater the diameter of the conduit the length of back set increases. Without the diameter size of the conduit, an answer can not be given.
A trade size hole for a 2-1/2" EMT conduit connector, the hole needs to be 2-7/8" in diameter. A 3" rigid conduit can also use this size hole without the lock nuts falling into the hole.
Normally the fixtures come with a grounding screw that you attach the grounding wire to. If the box you attaching the fixture to is metal and there is no grounding wire present then the grounded conduit should ground you fixture.
Conduit is not required for residential electrical IF THE WIRING IS BEHIND THE WALL. If it's exposed wiring, you'll need to use conduit.
You do not use a ground wire in the connection from the meter base to the distribution panel. A bonding wire may be required if the service is using PVC conduit.
Depends on the diameter of the conduit. Try for 1/4" larger diameter drill bit.
Not normally. An elaboration of what circuits are in the conduit and what type of conduit it is would be useful, though, and necessary to give a definitive answer.