For a #12 copper wire, in most areas of the US, branch circuit overcurrent protection shall not exceed 20 amps.
Check your local electrical code with any amendments to be sure! As always,
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS. If you do this work yourself, always turn off the power at the breaker box/fuse panel BEFORE you attempt to do any work AND always use a meter or voltage indicator
to insure the circuit is, in fact, de-energized.
A #8 copper conductor with an insulation rating of 75 or 90 degrees C are both rated at 45 amps.
#6 copper wire is normally used for 60 amp breakers.
100 amp
30 Amp.
Use only AWG # 10 copper.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
Depends on the wire size used in the circuit. If you use AWG # 14 wire you must use a 15 amp breaker. If it is wired with AWG # 12 wire then you use a 20 amp breaker. If a AWG # 10 wire is used then a 30 amp breaker is required. The breaker protects the wiring from overheating so you must use the proper size breaker for the wire used.
Depends on the size of the wire going to the A/C. If the wire is AWG #10 you cannot install a 40 amp breaker. If the wire is AWG #8 you can.
I think you mean either what is the correct size or minimum wire size needed when a branch circuit is protected by a 20 A breaker. The size is 12 American Wire gauge (AWG). 14 AWG is used for 15 A circuit and 10 AWG for a 30 A breaker. The lower the gauge the larger the cross-section of the wire.
AWG # 10 wire.
Use only AWG # 10 copper.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
Depends on the wire size used in the circuit. If you use AWG # 14 wire you must use a 15 amp breaker. If it is wired with AWG # 12 wire then you use a 20 amp breaker. If a AWG # 10 wire is used then a 30 amp breaker is required. The breaker protects the wiring from overheating so you must use the proper size breaker for the wire used.
For typical residential house wiring 12 AWG wire is required for a 20 Amp breaker. If you change out the breaker for a 25 A breaker you would have to rewire the circuit with 10 AWG. In that case you could up the breaker to 30 Amps. All outlets and switches should be rated at the same voltage and current as the breaker.
Depends on the size of the wire going to the A/C. If the wire is AWG #10 you cannot install a 40 amp breaker. If the wire is AWG #8 you can.
Use AWG #10 wire on a 20 amp breaker.
Normally AWG #10 wire on a 30 amp breaker but it really depends on the size of the pump. The pump manufacture will specify the size wire and size breaker needed.
I think you mean either what is the correct size or minimum wire size needed when a branch circuit is protected by a 20 A breaker. The size is 12 American Wire gauge (AWG). 14 AWG is used for 15 A circuit and 10 AWG for a 30 A breaker. The lower the gauge the larger the cross-section of the wire.
Yes, if you are using AWG # 10 wire. If you are using AWG # 12 then the answer is no you must use a 20 amp breaker. On AWG #14 wire you must use a 15 amp breaker.
10 AWG.
10 awg wire can have a breaker size of 30amps. It can actually carry more but as for codes the wire is usually allowed to carry 80% of its max capability which puts the breaker at a max size of 30 amps.