answersLogoWhite

0


Best Answer

NEC code table C10 has conduit fill charts. Google for it.

Per the table, 1 1/4" inch conduit can support 7 #4 cables. The 1 inch conduit allegedly can support 4 cables but it will be very tight and I would go for the extra room in a 1.25" conduit.

User Avatar

Wiki User

15y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

13y ago

Answer for USA, Canada and countries running a 60 Hz supply service.

It really depends on what type if insulation on the wire you are using and what type of conduit you are using. But, using the most common insulation in use today, THHN, and using the most common conduit in use today, EMT, you need 1 inch trade size (27mm) conduit.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

What size is the 4 wire? Larger wires fill the conduit faster. The answer is related to "percentage fill" Look up answers in the National Electric code NFPA 70.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size conduit do you need to install a 4 wire?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

When do you derate wires in conduit I know the code says more than 3 current carrying conductors but is there a length of conduit run when you should start to derate?

There are two things here to keep in mind. If you are trying to add more conductors to an existing conduit run use the cross sectional area of the conduit to see if more wires can be fitted. The second thing that's relates to length is the voltage drop at the load. To size the conduit work backwards from the load amperage to size the wires. If a long distance is involved a voltage drop calculation will be needed. Then select the conduit size to accommodate the wires recommended for that load amperage. The length of conduit run is not brought into the equation on de rating wire size it is always about keeping the voltage up at the load end of the run by increasing the wire size and selecting the proper conduit size for that wire.


What size conduit do you need to install a 0000 wire?

4/0 gauge wire, depending on its insulation type is rated from 230-260 amps. Assuming you are running a new power supply with the 4/0 wire, you will have a minimum or three 4/0 conductors and a ground wire for a single phase power supply and four conductors with ground for a three phase power supply. Three 4/0 wires require a minimum 2 inch conduit. Four 4/0 wires require a minimum 2 and 1/2 inch conduit. These conduit sizes I'm quoting come directly from the NEC, the National Electric Code. These sizes of conduit are determined by the basic rule that all the conductors in a conduit are not to exceed 40% of the volume of the pipe. The other 60% of air space is required for heat dissipation.


Is it permitted to use flexible conduit over 6 feet in length as a grounding means?

No. The new electrical code change does not allow any flexible conduit to be used as a ground means. It is now required to have a green ground wire pulled into the conduit with the other conductors in the flexible conduit. This grounded bonding conductor is not counted as wire fill when calculating the size of the flexible conduit to use


What size grounding wire do you use as the 4th wire running in your conduit from your 200 amp meter box to your 200amp service panel this is the ground wire from box to box?

You do not use a ground wire in the connection from the meter base to the distribution panel. A bonding wire may be required if the service is using PVC conduit.


When do you use a conduit bushing?

A conduit bushing is used when a conduit is terminated in a junction box or enclosure. Its purpose is to provide a smooth rounded surface so that when the wire is pulled into the conduit the insulation on the wire will not be damaged.

Related questions

Are additional parts needed to install this?

Yes, you will need a conduit connector and wire connectors to install the KitchenAid Architect II Microwave oven.


How many 10 stranded conductors can you pull in a 1 inch conduit?

Need to know the wire # size to compute wire fill in conduits


Does triplex wire need to be in conduit under a house?

Yes. If they are single wires they need to be in a conduit.


What size wire do you need going from a 20KW 83A generator to the main 200A automatic transfer switch?

In conduit? direct burial? distance?


What size conduit is correct for 10-3 gauge wire?

You can pull 10 #3 gauge wires in a 2 1/2" conduit.


What size conduit for 3 500 mcm wires?

The required size of a conduit raceway for a 3-5000 mcm wire is 300 kcmil. It maximizes the limits on the wire fill for raceways.


When do you derate wires in conduit I know the code says more than 3 current carrying conductors but is there a length of conduit run when you should start to derate?

There are two things here to keep in mind. If you are trying to add more conductors to an existing conduit run use the cross sectional area of the conduit to see if more wires can be fitted. The second thing that's relates to length is the voltage drop at the load. To size the conduit work backwards from the load amperage to size the wires. If a long distance is involved a voltage drop calculation will be needed. Then select the conduit size to accommodate the wires recommended for that load amperage. The length of conduit run is not brought into the equation on de rating wire size it is always about keeping the voltage up at the load end of the run by increasing the wire size and selecting the proper conduit size for that wire.


Com cast cable House to street 250 feet Can you run cable yourself What size wire Need conduit for underground?

Comcast will install the wiring for you. They do not allow homeowners to run their own wire because they lose quality control. Typically Comcast will run a 1 inch conduit for underground installations. The wire most commonly used it RG-6 quad. comcast doesnt install conduits anymore because it was just too costly so it is upto the homeowner to have have that installed by a general contractor and then comcast will have pull in the new line for you.


What size conduit do you need to install a 0000 wire?

4/0 gauge wire, depending on its insulation type is rated from 230-260 amps. Assuming you are running a new power supply with the 4/0 wire, you will have a minimum or three 4/0 conductors and a ground wire for a single phase power supply and four conductors with ground for a three phase power supply. Three 4/0 wires require a minimum 2 inch conduit. Four 4/0 wires require a minimum 2 and 1/2 inch conduit. These conduit sizes I'm quoting come directly from the NEC, the National Electric Code. These sizes of conduit are determined by the basic rule that all the conductors in a conduit are not to exceed 40% of the volume of the pipe. The other 60% of air space is required for heat dissipation.


What size conduit do I need for 6 wire. Being hooked up to a spa?

The minimum size you can use is 3/4 conduit. The code allows for a maximum of 4 each # 6 gauge wires in a 3/4 inch pipe. You'll likely be running 3 ea # 6s, two hots and the neutral and a #10 ground wire.


What size of copper wire can carry 30 amps?

Couple of things wrong here. 30 isn't a wire size. If you mean a wire that can carry 30 amps that would be # 10. Now it depends on how many # 10 wires you want to put into a conduit that governs the size of the conduit.


What size wire do you need for a 30amp 120 volt appliance. It will be run in steel conduit.?

A #10 copper wire with an insulation factor of 90 degrees C is rated at 30 amps. If you need the full 30 amps for the load use a #8 copper wire. Loaded to 80% of rating will give you 32 usable amps.