answersLogoWhite

0


Best Answer

This size service can be wired in a few combinations. Two parallel runs of 1250 MCM, three parallel runs of 600 MCM, four parallel runs of 350 MCM. Of the three choices the four runs of 350 MCM wires would be the easiest to handle if there are any bends in the service entrance conduit.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

7y ago

A ground fault breaker does not operate from a ground wire. The ground fault breaker operates from current Transformers that monitor the current flowing through the breaker. If the current becomes sufficiently high (depending on what the breakers trip point is set at) the CT's current will trip the breaker open. A CT's current output is from 0 to 5 amps.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size wire is needed for 1200 amp service?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

If you have 1200 watt generator how much will voltage drop with 100ft extension cord?

To answer this question more information is needed. The wire size of the extention cord is needed.


What size aluminum wire for 1200 amp service?

For Service Entrance Cable 600 kcmill (Thousands of circular mils).


What size USE wire is needed for 200 amps?

As a service entrance wire you need AWG # 3/0 gauge copper.


What size ground wire needed for a 200amp service panel in new jersey?

#6 bare copper wire.


What size ground wire is needed for 200amp service pannel in Chicago?

200 amp service in chicago uses 3 aught.


What is the wire size needed to feed a 400 amp service with parallel copper?

It depends on the length of the run


What size wire is needed for carrying 100 amps under ground?

To calculate the wire size, a system voltage is needed.


What wire size needed for 150 amp service at 325 feet Copper or Aluminum?

This is a voltage drop question. To receive an answer to this question the voltage of the service must be stated.


What size ground wire should you use on a 1200 amp service?

You need to say whether it's a 150 amp service or a 1200 amp service it has to be one or the other. <<>> A 1/0 copper conductor with an insulation factor of 90 degrees C is rated at 155 amps. There is no ground wire stated for a 150 amp service so the next size up is a 200 amp service. The ground wire for this size is #6 bare AWG. Without knowing what types of loads that are coming off of the distribution a reduced neutral can not be recommended. The neutral will be the same size as the service conductor which is 1/0.


What size service ground is needed for a 350 parallel service?

From the question it is hard to establish whether the service size is 350 amps or the service conductors are 350 MCM in parallel. If the service is 350 amps, the grounding conductor is #3 bare copper wire. Parallel 350 MCM conductors will allow for a 600 amp service. The grounding conductor for a 600 amp service is a #1 bare copper wire.


What size wire is needed for 1600 amp service?

4 sets of 750 mcm aluminum. Or four parallel runs of 600 MCM copper.


What size ground wire for 100a service?

A 100 amp residential service requires a size #8 copper wire, it should be insulated in green.