Best Answer

This is a voltage drop question and without a voltage the question can not be answered. As service voltages increase the wire size is allowed to be reduced. Assuming that the 200 amp service is for a home, the voltage of 240 volts will be used in the calculation.

A 3/0 copper conductor will limit the voltage drop to 3% or less when supplying 200 amps for 160 feet on a 240 volt system.

The code should be consulted on this installation as the utility company might not allow wires with no over current protection to come from the bottom of their meter to an underground service. There is a meter base in the market place that has an over current device mounted directly below the meter socket. This breaker will fulfill the requirement if the utility company says no to your original installation idea.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size wire would you run from 200 amp meter box underground 160 ft to a 200 amp breaker box?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is breaker size for 240 volt 9 KW?

The formula you are looking for is I = W/E.


What size wire for 28 amps?

Minimum size is 10 gauge with a 30 amp breaker. To be safe I would install an 8 gauge with a 40 amp breaker.


What size breaker would e needed for 10.8 amps?

In standard construction this would require a 15 amp breaker and 14 gauge copper wire.


What size wire would you use on a 30amp breaker?

AWG # 10 wire.


When installing a circuit breaker do you size the breaker to correct wire size or the device its controlling?

When installing a circuit breaker, you size the breaker based on the wire size. The breaker should be matched to the ampacity of the wire to ensure proper protection against overloads and short circuits. The device being controlled by the breaker is not a determining factor in sizing the breaker.


What size breaker do you use for a 100 amp sub panel?

A 100-A sub-panel would be fed from a 100-A breaker.


What is the standard to select circuit breaker?

Add up your amps to calculate your breaker size. Add up your loads (amps), divide by 0.8, and choose that size breaker. If that number does not correspond to a standard size breaker you go to the next higher standard size breaker.


What type of appliance would be use a two pole 50 amp breaker?

In North America this size breaker could be used on a welding machine. A range in the home would use a 40 amp two pole breaker.


What size breaker can you use on a 7500watt generator?

Depends on the wire size you are using. If the generator breaker is a 30 amp then install a 30 amp breaker.


If an electrician have a circuit that pulls a load of 10 amps what size breaker must that circuit be protected by?

If you are talking about a breaker in a house panel then a 15 amp breaker would be used. It is the smallest amperage breaker that you will find in a house panel.


What is the cable size for a 3KW motor 350 meter run for cable 240v?

Assuming being fed by c32 breaker for start load minimum cable size SWA is 70mm which will go to 456 meters


What size breaker does it take to run a outdoor well?

Normally AWG #10 wire on a 30 amp breaker but it really depends on the size of the pump. The pump manufacture will specify the size wire and size breaker needed.