Best Answer

The resistance for 400 ft. of 10 AWG copper is .4 ohms. This would be a voltage drop of (.4 x 20) or 8 volts. For 120 VAC service this is a 6% which is a bit high. At 240 volts it is 3%. At 8 AWG the resistance is .251 ohms which will give you better performance.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Will a 10 ga copper wire carry 20 amps at 400 ft?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What size wire is needed for a 200 amp residential service panel?

A 350 MCM copper wire with an insulation factor of 90 degrees C is rated at 325 amps. If the question is referring to maintaining a load of 300 amps then you have to up size the wire size because the conductor is only allowed to be loaded to 80%. A 500MCM copper wire with an insulation factor of 90 degrees C is rated at 395 amps x 80% = 316 amps.


What wire size to use from breaker box to earth ground rod?

The wire size used in a service entrance distribution panel is governed by the size of the services over current device. The larger the service, the larger the fault current could be, the larger the ground wire to carry the fault current to ground. If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod. The same goes from the service entrance panel on the pole.


What size wire needed for 200 amp service 400 feet away direct buried single phase 240 volt 3 wire?

Assuming you are working with 240v, you need 4/0 copper conductors.


What size wire needed for 100 amp service 700 feet away?

A 400 MCM copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 700 feet on a 240 volt system. This size will allow the conductor to be loaded to 80 amps. 100 x 80% = 80 amps. Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 100 amps then you would need to use a wire with a rating of 125 amps. 125 x 80% = 100 amps. A 600 MCM copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 700 feet on a 240 volt system.


400 amp service what size wire?

A 750 MCM wire with an insulation factor of 90 degrees C is rated at 500 amps. De rated to 80% will allow 400 amps on the wire. A 900 MCM wire with an insulation factor of 75 degrees C is rated at 520 amps. A 1500 MCM wire with an insulation factor of 60 degrees C is rated at 520 amps. Parallel 250 MCM will give you the same usage. A 250 MCM wire with an insulation factor of 75 or 90 degrees C are rated at 255 and 265 respectively. 255 x 2 = 510 x 80% = 408 amps. 265 x 2 = 530 x 80% = 424 amps.

Related questions

What size wire to run 400 ft from main panel need 60 amps?

Use AWG # 4 copper and you will have a 2.6% voltage drop which is acceptible.


What size conductor is needed to carry 25 amps 120 volt AC over 400 feet?

A #4 copper conductor will limit the voltage drop to 3% or less when supplying 25 amps for 400 feet on a 120 volt system.


What size wire is needed for a 200 amp residential service panel?

A 350 MCM copper wire with an insulation factor of 90 degrees C is rated at 325 amps. If the question is referring to maintaining a load of 300 amps then you have to up size the wire size because the conductor is only allowed to be loaded to 80%. A 500MCM copper wire with an insulation factor of 90 degrees C is rated at 395 amps x 80% = 316 amps.


What wire size to use from breaker box to earth ground rod?

The wire size used in a service entrance distribution panel is governed by the size of the services over current device. The larger the service, the larger the fault current could be, the larger the ground wire to carry the fault current to ground. If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod. The same goes from the service entrance panel on the pole.


What is the weight of 400 mcm copper wire per foot?

500mcm 37 strand copper wire = 1.544lbs/ft.


How much current does 300 sq mm cable carry?

A 228 sq mm conductor equates to 450 MCM. A conductor of 450 MCM is not a standard AWG wire size. A standard 400 MCM will carry 380 amps. A standard 500 MCM will carry 430 amps. Difference between 400 and 500 MCM amperage's is 50 amps. Transposing between the two amperage's of 50 amps will be 380 + 25 = 405 or 430 - 25 = 405 amps. This is a very rough calculated answer for the question.


What size wire needed for 200 amp service 400 feet away direct buried single phase 240 volt 3 wire?

Assuming you are working with 240v, you need 4/0 copper conductors.


What gauge of service wire for a 400 Amp single phase servce?

A 600 MCM copper conductor with an insulation factor of 75 or 90 degree C is rated at 420 and 455 amps respectively. This is very large diameter wire to handle. The best way of wiring this service is to use parallel runs. A 3/0 copper conductor with an insulation factor of 75 or 90 degrees C is rated at 200 and 210 amps respectively. So depending on the insulation of the wire that is used, a parallel wire configuration will give you a total of 400 at 75 degrees C or 420 at 90 degrees C.


What size wire needed for 100 amp service 700 feet away?

A 400 MCM copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 700 feet on a 240 volt system. This size will allow the conductor to be loaded to 80 amps. 100 x 80% = 80 amps. Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 100 amps then you would need to use a wire with a rating of 125 amps. 125 x 80% = 100 amps. A 600 MCM copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 700 feet on a 240 volt system.


What is the cable size for 90 kw motor?

Depends upon the voltage. The formula for amperage or (wire size) is Watts / Voltage. If the voltage is 220 volts, then the amperage would be over 400 amps. This would require a large wire size to run it. If it were 440 volts, the amperage would be 1/2 or 200 amps. That would require a smaller wire size. As the voltage goes up, the amperage goes down. At a thousand volts, the amperage would only be 90 amps. A wire gauge or size of a #2 would carry 90 amps for small distances.


What does 400 mcm copper wire way per foot?

1.385 pounds per foot


400 amp service what size wire?

A 750 MCM wire with an insulation factor of 90 degrees C is rated at 500 amps. De rated to 80% will allow 400 amps on the wire. A 900 MCM wire with an insulation factor of 75 degrees C is rated at 520 amps. A 1500 MCM wire with an insulation factor of 60 degrees C is rated at 520 amps. Parallel 250 MCM will give you the same usage. A 250 MCM wire with an insulation factor of 75 or 90 degrees C are rated at 255 and 265 respectively. 255 x 2 = 510 x 80% = 408 amps. 265 x 2 = 530 x 80% = 424 amps.