No. This practice is a violation of Article 210.19 (A) of the NEC. "Conductors of branch circuits supplying more than one receptacle for cord-and-plug-connected portable loads shall have an ampacity of not less than the rating of the branch circuit."

User Avatar

Wiki User

13y ago

What else can I help you with?

Continue Learning about Electrical Engineering

What are skirted receptacles?

A commercial receptacle that is used to prevent arching.


Can you feed multiple outlets to one GFCI outlet near the sink?

code states that if a water source such as a sink is within 6 feet of a receptacle, that recetacle (s), must be protected by a GFCI receptacle. I believe the actual distance is 5 feet. Please forgive me if I'm wrong. But the NEC also requires that ANY counter top receptacles in a kitchen and receptacles ANYWHERE in a bathroom must be GFCI protected. More directly to your question, ordinary receptacles can be protected from a GFCI receptacle if properly wired. They are designed to do that. It is a way to save money. You may also consider a GFCI breaker if you have many receptacles to protect. I was told once that there is a limit of 3 "piggy backed" receptacles per GFCI but I have never seen that in the NEC.


How do you wire receptacles in series?

Receptacles are not wired in series. Receptacles are actually wired in parallel, what this means is that all phase wires (black) in a receptacle's box should terminate to the brass screws on each device, and all neutral (white) wires in the box should terminate on the silver screws on each device.


How do you install multiple GFCI receptacles?

A GFCI receptacle can extend its protection to regular receptacles connected to the output side of the GFCI. Each actual GFCI receptacle should be directly connected to a breaker in electric panel.


Can reverse polarity burn a tv set?

If, by 'reverse polarity', you mean the accidental reversal of the line and neutral conductors at the socket outlet or receptacle, then the answer is no.

Related Questions

How do you wire receptacles in series?

To wire receptacles in series, connect the hot wire from the power source to the first receptacle, then connect a jumper wire from the first receptacle to the second receptacle, and so on for each additional receptacle in the series. Finally, connect the neutral wire from the power source to the last receptacle in the series.


What are skirted receptacles?

A commercial receptacle that is used to prevent arching.


WHAT IS THE FUNCTION OF RECEPTACLE?

The function of the seminal receptacles is to receive semen.


Where can one find more information on receptacles?

Information on receptacles can be found on the websites of companies that sell receptacles. For example, if the receptacle one has in mind is a waste paper bin, visit Amazon and find a waste paper bin for sale. Then one will find information about that receptacle, for example.


What is the function of receptacles of a flower?

The Receptacle of a flower is the bottom of the flower. It holds everything together. reproductive parts of a plant. Receptacle is female


What is the reference to female when explaining electrical receptacles?

No. The term female receptacle means there is a hole and a male receptacle means it has a pin sticking out.


What might happen if the line and load connetions of a feedthrough gfci receptacle were reversed?

Most probably the receptacles downstream from the GFCI would not be protected by the GFCI receptacle.


What would cause screws on receptacle to become red hot?

There are three major causes of hot screws on a receptacle. 1.. Overcurrent: Receptacles are usually rated at 15 amps, occasionally 20 amps. If the circuit breaker feeding it is too large or faulty, the receptacle could overheat due to the loads it is feeding. 2.. Loose screws at the receptacle. This condition leads to arcing at the receptacle and evetually, fire. 3.. Copper contamination. Carbonization or crystalization can occur on the conductors at the screw terminal. This can usually be cleaned up with emery cloth.


Gfi receptacle first in a line of seven other receptacles in new construction that works fine without the load of the other receptacles but does not work when you add the additional receptacles?

There must be leakage current in the down stream receptacles It is going to be a trial and error method of finding the leak. Remove the GFI and make a through connection to the downstream receptacles Now go to first receptacle and install the GFI. If it holds the fault is further down stream. Keep going down the line until you find the fault. When the GFI trips and won't reset it will be the up stream feeder. Check the feeder wire for cuts or scrapes in the insulation. Replace this feeder.


Where must GFCI receptacles be installed in residential garages?

All receptacles in a garage must be GFCI protected by code. Typically, the first receptacle in the circuit (location is irrelevant) must be a GFCI, then all others down stream in the circuit will be protected, and can be common receptacles.


What is the ampere specification of switches and sockets used in house wiring?

In North America the standard receptacles and switches are rated at 15 amps. A dryer receptacle is rated at 30 amps and a range receptacle is rated at 50 amps. New code rules are allowing 20 receptacles in some specific locations.


What are the two basic specifications that electrical receptacles are based on?

One basic specification that electrical receptacles are based on is the amount of amperage that the receptacle can legally handle. The other basic specification is the amount of voltage that the receptacle can legally handle. This is the reason that there are so many different types to choose from. When buying a receptacle you should be armed with the knowledge of what the voltage is going to be and what the load amperage is going to be to get the proper receptacle. Each receptacle has different pin configurations for voltage and amperage. This is a safety factor so that inter changeability can not happen.