Ground wire is loose or disconnected somewhere in that circuit.
Not if the GFCI breaker is supplying the circuit you are wanting to put the GFCI receptacle into.
No, except that you insert the wires into the holes on the back of the outlet. The power in connects to the LINE side of the outlet and power out connects to the LOAD side of the outlet. This is clearly marked on the back of the outlet. This will not only protect the outlet with the GFCI installed but all outlets receiving their power from that GFCI. If you do not want to protect the outlets receiving power from the outlet then connect that outgoing wire to the LINE side also. But know that only the outlet with the GFCI will be protected and all other outlets will not be GFCI protected.
I assume you are hard wiring it and not plugging it in. The power coming into the GFCI outlet connects to the line side of the GFCI outlet. If you want the outdoor timer protected by the GFCI then connect the wire going to the timer to the load side of the outlet. If you do not want the timer protected then connect it to the line side. On the back of the GFCI if you look closely you will see Line & Load marked on the back.
A down stream receptacle that is connected to the upstream GFCI will be protected. If the downstream receptacle senses a fault the upstream GFCI will trip.
Ground wire is loose or disconnected somewhere in that circuit.
Not if the GFCI breaker is supplying the circuit you are wanting to put the GFCI receptacle into.
You can determine if an outlet is after a GFCI by pressing the "test" button on the GFCI outlet. If the GFCI trips and cuts off power to the outlet, then that outlet is downstream from the GFCI. If power is not cut off, then that outlet is upstream from the GFCI.
No, except that you insert the wires into the holes on the back of the outlet. The power in connects to the LINE side of the outlet and power out connects to the LOAD side of the outlet. This is clearly marked on the back of the outlet. This will not only protect the outlet with the GFCI installed but all outlets receiving their power from that GFCI. If you do not want to protect the outlets receiving power from the outlet then connect that outgoing wire to the LINE side also. But know that only the outlet with the GFCI will be protected and all other outlets will not be GFCI protected.
Yes you can. Lots of blow dryers have GFCI protection built in.
I assume you are hard wiring it and not plugging it in. The power coming into the GFCI outlet connects to the line side of the GFCI outlet. If you want the outdoor timer protected by the GFCI then connect the wire going to the timer to the load side of the outlet. If you do not want the timer protected then connect it to the line side. On the back of the GFCI if you look closely you will see Line & Load marked on the back.
It is recommended to have GFCI protection for all electrical outlets in a garage to help reduce the risk of electric shocks. This would typically involve installing a GFCI outlet at the beginning of the circuit to protect the rest of the outlets downstream.
Click the link.
A down stream receptacle that is connected to the upstream GFCI will be protected. If the downstream receptacle senses a fault the upstream GFCI will trip.
GFCI Breakers are quite a bit more expensive than a GFCI outlet. More often than not a typical residence will need only a handful of GFCI outlets that combined together will be cheaper than a GFCI breaker. If you need to protect a series of outlets with GFCI protection you can simply connect the rest of the outlets on that same circuit downstream from the first outlet on the line and make that the GFCI. All you have to do is connect all the other outlets to the LOAD side of the GFCI outlet. If a GFCI fault occurs in any of the outlets down stream they will trip that very first GFCI plug you placed and keep you safe.
No, a GFCI outlet is designed for use with standard 120-volt circuits. Attempting to use a GFCI outlet with a 240-volt split circuit could cause damage to the outlet, the circuit, and could present a safety hazard. It is not recommended to use a GFCI outlet in this manner.
If the wall receptacle has tripped but not at the circuit breaker, it could be a faulty GFCI outlet. Try pushing the reset button on the GFCI outlet itself to restore power. If that doesn't work, you may need to replace the GFCI outlet. Make sure to turn off the power at the breaker before attempting any repairs.