A 100-A sub-panel would be fed from a 100-A breaker.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
Yes, but they obviously cannot be simultaneously loaded their maximum loads because the 400-amp breaker will blow well before that. Similarly, you can have multiple 100-amp panels fed from a 200-Amp main breaker, knowing that you will NEVER have 100 amps running in all panels at the same time.
You can reduce the breaker size because that limits the current that can reach the main panel. There is no safety issue other than the significant danger in an unskilled person changing out a main breaker.
Not unless you change the wiring for that circuit. The breaker protects the wiring and if you install a 40 amp breaker on a 15 amp wire circuit you will have a fire in your home.
A 100-A sub-panel would be fed from a 100-A breaker.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
probally about 100 dollars
If a 100 amp breaker keeps tripping there is an overload on the system.
Yes, a 100 amp main panel can have 2 separate 50 amp circuits protected by 50 amp breakers. This configuration allows for two separate circuits drawing up to 50 amps each from the main panel without overloading the panel's 100 amp capacity.
Yes, but they obviously cannot be simultaneously loaded their maximum loads because the 400-amp breaker will blow well before that. Similarly, you can have multiple 100-amp panels fed from a 200-Amp main breaker, knowing that you will NEVER have 100 amps running in all panels at the same time.
You can reduce the breaker size because that limits the current that can reach the main panel. There is no safety issue other than the significant danger in an unskilled person changing out a main breaker.
Not unless you change the wiring for that circuit. The breaker protects the wiring and if you install a 40 amp breaker on a 15 amp wire circuit you will have a fire in your home.
You can typically determine the amperage of an electrical panel by looking at the main breaker. A 100 amp panel will have a main breaker rated at 100 amps, while a 200 amp panel will have a main breaker rated at 200 amps. Additionally, the size and number of circuit breaker slots can also be indicators of the amperage rating.
There are two things to think about here. First of all a 200 amp breaker will not physically fit into a 100 amp panel. This is so designed because the panel buss is not designed to conduct 200 amps before the current is cut off. A 100 amp rating on the panel is the maximum amount of current that the manufacturer states, that can be handled safely. Second if the 200 amp breaker is in the main panel then everything downstream from that breaker has to be rated for 200 amp conductivity. The wire size will have to be 3/0 from the breaker to the first over current device in the sub panel which will be the sub panel's main breaker. The sub panel can not be a load center but will have to be a combination panel. I doubt that the 100 amp sub panel's main breaker lugs would be large enough to connect the 3/0 cable.
Yes. Many installations have breaker totals higher that the main breaker of the panel. It is worked on a percentage basis. Not all of the breakers will be on at the same time. In a home, on a 100 amp panel the average load is 50 - 60 amps. The 100 amp main breaker is protecting the 100 amp rated panel board. If the load current goes higher that the panel board is rated at, the main breaker will trip to protect the board.