A 100-A sub-panel would be fed from a 100-A breaker.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
Yes, but they obviously cannot be simultaneously loaded their maximum loads because the 400-amp breaker will blow well before that. Similarly, you can have multiple 100-amp panels fed from a 200-Amp main breaker, knowing that you will NEVER have 100 amps running in all panels at the same time.
You can reduce the breaker size because that limits the current that can reach the main panel. There is no safety issue other than the significant danger in an unskilled person changing out a main breaker.
Not unless you change the wiring for that circuit. The breaker protects the wiring and if you install a 40 amp breaker on a 15 amp wire circuit you will have a fire in your home.
A 100-A sub-panel would be fed from a 100-A breaker.
The maximum current capacity of a 100 amp circuit breaker is 100 amps.
The maximum amperage capacity of a 100 amp Pushmatic breaker is 100 amps.
The maximum amperage capacity of the main breaker in a 100 amp sub panel with a main breaker is 100 amps.
The maximum amperage capacity of a 100 amp panel with a main breaker is 100 amps.
The maximum amperage capacity of a 100 amp main breaker in an electrical panel is 100 amps.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
probally about 100 dollars
No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
If a 100 amp breaker keeps tripping there is an overload on the system.
Yes, a 100 amp main panel can have 2 separate 50 amp circuits protected by 50 amp breakers. This configuration allows for two separate circuits drawing up to 50 amps each from the main panel without overloading the panel's 100 amp capacity.
The recommended wire size for a 100 amp breaker is typically 2-gauge copper wire or 1/0-gauge aluminum wire.