It is rated at 20 amps. Code states that conductors should only be loaded to 80% so continuous load will be 20 x .8 = 16amps
122/208
The ideal temperature for an electrical panel should generally be between 20°C to 30°C (68°F to 86°F). However, temperatures should not exceed 50°C (122°F) to prevent overheating and potential damage to electrical components. Regular monitoring and maintenance are essential to ensure that the panel operates within safe temperature limits.
NEC recommends maximum allowable voltage drops not to exceed 3% on a branch circuit. For feeder/ branch combos the NEC recommends that the voltage shall not drop by more than 5% to the furthest outlet. The main consideration that is enforced is NEC 250-122. You must compensate your grounding conductor when you increase in conductor size to compensate for voltage drops. Direct bury or conduit: #4/0 copper provides for 2.95% #2/0 copper provides for 4.35% #1/0 copper provides for 5.19% Interestingly enough, using a separate calculator 3/0 copper with 3% voltage drop can be 780.5 feet long.