You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
No more than 13 maximum on a 20 amp circuit.
Depends on the wire size you are using. If the generator breaker is a 30 amp then install a 30 amp breaker.
AWG 12/2 requires the use of a 20 amp single pole breaker.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
On a 15 amp household breaker there is no terminal on the in feed of the breaker. The breaker either plugs into the distribution panel's bus bar or it bolts to the distribution's bus bars. The feed conductor connects to the load side of the breaker at its terminal lug.
The breaker you use is determined by the size of the wire in the wall not by what is being connected to that circuit. If you have 14/2 wire then use a 15 amp breaker. If you have 12/2 wire then use a 20 amp breaker. The breaker protects the wiring not the item connected.
A 32 amp fixture can not be fed from a 20 amp breaker as the breaker will trip every time.
A 15 amp breaker is not sufficient for a 225 amp load. You would need a breaker that matches the load current, such as a 225 amp breaker. Using a 15 amp breaker for a 225 amp load would cause the breaker to trip immediately due to overcurrent.
Replace the 30 Amp Breaker with a 15 Amp breaker.
On a 15 amp breaker, you can draw up to 120 volts in a standard residential circuit. The voltage remains constant at 120 volts, but the amperage capacity is what is limited by the 15 amp breaker.
It is not recommended to replace a 20 amp breaker with a 30 amp breaker for a 220 volt machine. The breaker size needs to be compatible with the current draw of the machine to ensure safe operation and prevent electrical hazards. Using a larger breaker than recommended could lead to overheating and potentially damage the machine or cause a fire hazard.
A 50 amp breaker is an overcurent device.
Yes, a 30 amp double pole breaker would be suitable for a 4800 watt wall heater. Since watts equals volts multiplied by amps, this wall heater on a 240-volt circuit would draw 20 amps (4800 watts/240 volts), which is less than the 30 amp capacity of the breaker.
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
NO!
Yes, a 30 amp breaker is a 30 amp breaker. It must however be able to fit the box it is installed in.