answersLogoWhite

0


Best Answer

Yes, If it is unfinished. Reference National Electrical code NFPA 70 for additional details.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Is a ground fault required in a basement?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Where is your basement in a house?

The basement is the level in your house below ground level. To say it another way, you would be below the ground if you were in a basement.


Is a ground fault protection for equipment required even if the neutral will not be used?

Yes, ground fault protection for equipment is requiredeven if the neutral will not be used.However, the question implies that it might not be required if there is a neutral. That is not true. With two exceptions, ground fault protection is always required in the US, and it is probably required in other countries as well.The exceptions are the use of an electric cooking range, and an electric clothes dryer. In those cases, the US NEC allows the neutral conductor to also be the ground fault conductor, except for the case where the range or dryer is in a mobile home. In the case of the mobile home, the ground fault conductor and the neutral conductor must be maintained separate and distinct all the way back to the distribution panel.In every other case, including where local code overrides the US NEC's exceptions, it must be understood that ground fault protection (protective earth ground) is not the same as neutral, even though the neutral conductor is grounded.


What is the different between basement and semi basement?

One or more floor of a building that are completely below the ground floor is basement. A floor of a building that is half below ground, rather than entirely such as a basement is semi basement.


What are the release dates for Ground Basement Roof - 2012?

Ground Basement Roof - 2012 was released on: USA: November 2012


Where is the basement located in most houses?

In most homes the basement is very common and can be found underneath the main floor. The basement relative to the ground is usually found underneath ground level.


How do you wire a ground fault switch?

To replace the wire ground fault switch, you need to switch off electric power from the source. After switching it off you can use the screwdriver to open screw and remove the faulty switch and replace it with a good one. <<>> There is no such a device as a ground fault switch. There is a ground fault breaker and a ground fault receptacle.


What is a basement appliance that can heat your house?

A basement of a house is the room or space that is below ground level. A basement appliance that can heat your house is a furnace.


What do ground fault relays do?

Ground fault relays sense ground faults in the circuit and trigger a circuit breaker to trip off


What is a room under the ground called?

A room under the ground is typically called a basement or cellar.


Can you install two ground wires in the same raceway?

There should be no reason to install two ground wires in the same conduit. Code requires that only a single path should be required if it is to carry a fault current. This ground wire should be single and continuous from the device back to the distribution panel. It is the fault current that is carried on the ground wire that trips the breaker or fault protection device. Don't confuse grounding wires with bonding wires.


What is the under ground basement in Pokemon Gold?

naab


What are the types of faults in ehv transmission lines?

The three types are Line to ground faults line to line fault double line to ground fault three phase line to ground fault