177 mm squared is equal to 350 MCM AWG.
Using the AWG for wire sizes only goes up to 4/0. After that the increases use MCM to size the wire. So your 262 MCM wire size will be same in AWG. There is no 262 MCM in the North American market place. It goes in 50 MCM increments starting at 250 MCM , 300 MCM, 350 MCM, 400 MCM right up to 2000 MCM cable.
530 amps in average conditions, more in cold weather. <<>> The closest conversion will be; 405 mm2 is equal to 800 MCM AWG. A 800 MCM aluminium conductor with an insulation factor of 90 degrees C is rated at 445 amps.
A 350 MCM copper conductor with an insulation rating of 90 degree C is rated at 350 amps.
6 AWG will handle 50 amps with a voltage drop of about 4 volts. If you go to 4 AWG and limit to 50 amps your voltage drop will be 2.5 volts.
177 mm squared is equal to 350 MCM AWG.
Using the AWG for wire sizes only goes up to 4/0. After that the increases use MCM to size the wire. So your 262 MCM wire size will be same in AWG. There is no 262 MCM in the North American market place. It goes in 50 MCM increments starting at 250 MCM , 300 MCM, 350 MCM, 400 MCM right up to 2000 MCM cable.
There is no defined AWG for 350 MCM. The American Wire Gauge stops at 0000 (4/0), and 350 MCM is bigger than this. An approximate conversion would be 6/0, if there were such a thing. Extrapolating out from 4/0, 6/0 is 334.8 MCM, and 7/0 is 422.2 MCM. These wire sizes don't exist of course, and don't exactly match 350 MCM anyway.
A 228 sq mm conductor equates to 450 MCM. A conductor of 450 MCM is not a standard AWG wire size. A standard 400 MCM will carry 380 amps. A standard 500 MCM will carry 430 amps. Difference between 400 and 500 MCM amperage's is 50 amps. Transposing between the two amperage's of 50 amps will be 380 + 25 = 405 or 430 - 25 = 405 amps. This is a very rough calculated answer for the question.
530 amps in average conditions, more in cold weather. <<>> The closest conversion will be; 405 mm2 is equal to 800 MCM AWG. A 800 MCM aluminium conductor with an insulation factor of 90 degrees C is rated at 445 amps.
A 350 MCM copper conductor with an insulation rating of 90 degree C is rated at 350 amps.
the lower the number, the larger the wire. 0 AWG is larger than 4 AWG More information: The above answer is correct but I wish to add more information. What you are calling 0 AWG is usually written as 1/0 and called "one ought". From there the numbers get larger: 1/0, 2/0 (read "2 ought"), 3/0, and 4/0. From there wires are written in there MCM size or kcmils (kilo-circular-mills) which stands for thousand circular mills, the same as MCM. That's a lot of useless information unless you are a competent electrician. I just wanted to clarify that 0 AWG is commonly called 1/0, or "one ought."
the lower the number, the larger the wire. 0 AWG is larger than 4 AWG More information: The above answer is correct but I wish to add more information. What you are calling 0 AWG is usually written as 1/0 and called "one ought". From there the numbers get larger: 1/0, 2/0 (read "2 ought"), 3/0, and 4/0. From there wires are written in there MCM size or kcmils (kilo-circular-mills) which stands for thousand circular mills, the same as MCM. That's a lot of useless information unless you are a competent electrician. I just wanted to clarify that 0 AWG is commonly called 1/0, or "one ought."
6 AWG will handle 50 amps with a voltage drop of about 4 volts. If you go to 4 AWG and limit to 50 amps your voltage drop will be 2.5 volts.
A 300 MCM copper conductor with an insulation rating of 90 degrees C is rated at 320 amps. Parallel the feeders to obtain a total of 640 amps. This will be acceptable as service feeders for a 600 amp service.A 400 MCM aluminium conductor with an insulation rating of 90 degrees C is rated at 305 amps. Parallel the feeders to obtain a total of 610 amps. This will be acceptable as service feeders for a 600 amp service.
depends on the amperage. 14 AWG for 15 amps, 12 AWG for 20 amps, 8 AWG for 50 amps.
A parallel run of 750 MCM AWG conductors will handle 1000 amps. if we want 1000amps to flow, 250sqmm cable is enough.