It is a wire with special insulation that protects it under ground. On the wire there will be a stamp "UF" or underground feeder. That means that it can be buried directly in the earth.
Chat with our AI personalities
In conduit? direct burial? distance?
12/3 will work.
Answer for USA, Canada and countries running a 60 Hz supply service.Termination of direct burial wire is done as you would terminate any other set of wires. However, direct burial does not mean you can direct bury the terminations. The wire must be brought into a building by an approved method; or the wire must be brought into a box designed for burial, with the box accessible from the surface of the ground; or the wire must be brought into a piece of equipment that is partially buried and designed for that purpose.In no case should the wire reach a depth of less than the minimum required depth for the installation without being protected by conduit. And in no case should the wire enter a building without conduit unless installing UF cable is allowed without conduit in the installation.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.
Wire in conduit for underground feeders has to have an insulationrating for wet and damp locations. In the marketplace there is also wiring thathas an insulation rating for direct burial that does not need to be installed into conduit.
USE, USE-2, and UF