If there is a possibility of both operating simultaneously, then a 100 amp breaker (actually 80 amp if you can find one), and appropriate wiring would be required. Even if they were not expected to operate simultaneously, it would be prudent to wire as if they were.
The dryer tripped the breaker. Have it repaired. Don't try to use it again. You could cause a fire.
A dryer requires a 30 amp receptacle. This will be to receive a four blade dryer plug. The wire needed will be a three copper wire #10 cable set with a bare #14 copper ground wire. The breaker will be a two pole 30 amp breaker.
An electrician would put in two separate circuits since there is no telling in future that gas dryer might be replaced. You need to look at the breaker protecting the circuit and see if the current from the dryer and washer when added together don't exceed 80% of the breaker rating. Also the start up current for the dryer tumbler and washing machine motor don't add up to more than the breaker rating when added together. This is where problems will occur since start up currents may be 6 times running current.
Yes, it would appear that one side of the main is open at the fuse, breaker, drop conductors, or transformer.
In North America the standard sizes for breakers are 15, 20, 30, and 40 amps. The 15 amp size breaker is used in general circuit wiring. The 20 amp size breaker is used for dedicated appliance receptacles, hot water tank and baseboard heating. The 30 amp size breaker is used for a clothes dryer. The 40 amp size breaker is used for the electric range.
There is a risk of electrical shock or fire if a 240V breaker is on and someone attempts to turn on the clothes dryer, as the high voltage could create a dangerous situation. It's important to ensure appliances are compatible with the voltage supply and that safety precautions are observed when working with electricity.
Answer for USA, Canada and countries running a 60 Hertz supply service.The breaker required for a dryer is a two pole 30 amp breaker which will feed a 3 conductor #10 cable.
The dryer tripped the breaker. Have it repaired. Don't try to use it again. You could cause a fire.
Installing a 30A 240V GFI breaker for a dryer should be fine as long as the wiring and dryer itself are compatible with the breaker. The GFI breaker is designed to protect against electrical faults and should not be affected by the cycles of the dryer. Make sure to follow the installation instructions carefully to ensure proper functioning.
A dryer requires a 30 amp receptacle. This will be to receive a four blade dryer plug. The wire needed will be a three copper wire #10 cable set with a bare #14 copper ground wire. The breaker will be a two pole 30 amp breaker.
Could be but you could also have a weak breaker that will no longer hold the load of your dryer. That is if your talking about your dryer breaker tripping. If your "main breaker" is tripping you have a different problem. Call an electrician in that case. A plugged up dryer shouldn't be tripping your main
Yes, 60 amps is typically enough to run a household dryer. Most dryers require around 30 amps to operate, so 60 amps should provide sufficient power for the dryer along with other household electrical needs. Just ensure that the wiring and circuitry in your home can handle the load.
If you are referring to a cloths dryer, the answer depends on the requirements of the dryer. Most dryers require AWG#10 wire with a 30 amp fuse. If the wiring is AWG#12 then use a 20 amp breaker but never use it on AWG#10 which requires a 30 amp breaker. If you are referring to a hair dryer then yes a 20 amp breaker is fine.
If the circuit breaker to a dryer, or to any load, keeps getting hot and trips the breaker, then either the load is pulling too much current or there is a loose connection in the breaker or breaker panel. Either condition must be fixed to reduce the risk of fire.
The double 30 amp breaker for an electric dryer is typically located in the electrical panel or circuit breaker box of the house. It is used to provide the necessary power for the dryer to operate safely and efficiently. If you are unsure where it is located, it is recommended to consult with a qualified electrician for assistance.
Not advisable. Both units consume huge amounts of Amps (amperes = current) and the normal 20 or 30 amp breaker may not sustain prolonged operation of both. Where I live, we have two electric meters ... one just for the water heater, the other for the house and all it's electrical needs (except for the water heater).
No, the dryer needs 120 volts supplied by the neutral third wire, along with the 240 volts for the dryer element. One of the two 240 volt supply conductors is used with the neutral to supply 120 volts to the controls and the drum motor. That is why a three wire cable is needed.