Best Answer

The minimum size you can use is 3/4 conduit. The code allows for a maximum of 4 each # 6 gauge wires in a 3/4 inch pipe. You'll likely be running 3 ea # 6s, two hots and the neutral and a #10 ground wire.

User Avatar

Wiki User

βˆ™ 14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size conduit do I need for 6 wire. Being hooked up to a spa?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Is it legal to support a conduit from another conduit of the same size?

No, the conduit has to be supported individually from a supportive structure. The spacing of the strapping is related to the size of the conduit.


What size foot valve do you need?

The same size as the pipe it is hooked up to in the well.


What size drill bit do you need for a piece of conduit?

Depends on the diameter of the conduit. Try for 1/4" larger diameter drill bit.


What size conduit for 400 amp service?

4 inch rigid conduit


What size conduit for 400amps?

The sizing of conduit systems that wire has to be pulled into is dependant on the physical size of the conductor being drawn into the conduit. The second governing factor is the conductor count of the specific conductor that is needed. A 500 MCM copper conductor with an insulation factor of 90 degrees C is rated at 430 amps. This is where the conductor count is need by the service, as to whether the service is single or three phase. In this specific case, the electrical code will allow both single and three phase installations to use the same size conduit. A maximum total of four 500 MCM conductors can be drawn into a 78 mm diameter conduit.


What is the actual hole size for 1 inch conduit?

Actual hole size for 1 inch conduit is 1.362"


What size conduit is needed for wiring in Indian houses?

The size of conduit is based on the size of the wires in it. The size of the wires depends on the load connected in the house. Without these other two values an answer can not be given.


What size conduit for 200 amps?

120mm


What size should under ground conduit be from pole to meter base?

For new 200 amp services the conduit size should be 3 inch PVC.


What size amp do you need with one 12 inch sub 1200 watts peak and 400w RMS?

a 400 watt 2 channel amp should do fine. all you need to do is bridge the sub when it is being hooked up


What is the hole size required for a 2.5 conduit?

A trade size hole for a 2-1/2" EMT conduit connector, the hole needs to be 2-7/8" in diameter. A 3" rigid conduit can also use this size hole without the lock nuts falling into the hole.


What is the multiplier for 45 degree offset in conduit bending?

Back set for all conduit sizes is not the same. The greater the diameter of the conduit the length of back set increases. Without the diameter size of the conduit, an answer can not be given.