Yes, a #10 wire will carry 30 amps for 30 feet. If the load is rated as continuous then the wire will have to be derated to 80% capacity which will leave you with 24 workable amps. If the load demands currents higher that 24 amps then you will have to go to the next wire size up which is a #8 which is rated at 45 amps.
AWG 10.
A 3/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 150 amps for 150 feet on a 240 volt system. This size will allow the conductor to be loaded to 120 amps. 150 x 80% = 120 Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 150 amps then you would need to use a wire with a rating of 190 amps. 190 x 80% = 152 amps A 4/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 190 amps for 150 feet on a 240 volt system.
# 4 copper wire short distance.
The V stands for volts and A is amps. If for example you have a 12kVA device and are running off a voltage of 120 volts then Amps = 12000/120 = 100. You then use the calculated amps in a wire size table to get the correct size.
AWG # 6 copper
Yes, a #10 wire will carry 30 amps for 30 feet. If the load is rated as continuous then the wire will have to be derated to 80% capacity which will leave you with 24 workable amps. If the load demands currents higher that 24 amps then you will have to go to the next wire size up which is a #8 which is rated at 45 amps.
You would need to use a wire size that is rated for at least 40 amps to be safe and to meet the requirements of the air conditioner. A common wire size for this application would be 8 AWG copper wire, which is rated for 40 amps.
AWG 10.
15 amps.
15mm approx.
10 guage
A 3/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 150 amps for 150 feet on a 240 volt system. This size will allow the conductor to be loaded to 120 amps. 150 x 80% = 120 Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 150 amps then you would need to use a wire with a rating of 190 amps. 190 x 80% = 152 amps A 4/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 190 amps for 150 feet on a 240 volt system.
For a 50 feet distance with 120 volts and 12 amps, you should use a 14-gauge wire to ensure electrical safety and efficiency. A 14-gauge wire is rated to handle up to 15 amps for household wiring applications.
# 4 copper wire short distance.
The V stands for volts and A is amps. If for example you have a 12kVA device and are running off a voltage of 120 volts then Amps = 12000/120 = 100. You then use the calculated amps in a wire size table to get the correct size.
12-2 (#12-2 conductor) wire doesn't "pull" 20 amps. However, it's ampacity rating is that of 20 amps. #12 copper wire is rated for a total load of 20 amps. So, always use a 20 amp breaker with it.