Generally speaking, you would find conductor ampacity (the amount of current it can handle continuously) in Table 310.16 of the NEC (National Electrical Code). The numbers in the table are good as long as you don't go over the stated number of conductors at the top of the table and the 86 degree Celsius ambient temperature. If anything changes, use the adjustment factors for conduit fill and ambient temp.
However, with all the possible other applicable sections of the NEC, it really depends on the type of load and howand where the cable is fixed because its operating temperature will depend on whether it is enclosed in a duct, is buried underground or is outside in the open air.
For a typical load, not knowing anything else about it, I would multiply the load (in amps) by 1.25 and find a wire with at least that ampacity.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
The wire size is based on the amperage of the load. With this amperage the electrical code book has tables that show the maximum amp capacity that each conductor can legally carry. With this wire size additional calculations are made if there is distance involved to reduce voltage drop of the wire. Also calculations are made to readjust the size of the wire if the ambient temperature that the wire passes through are higher than normal.
125% for continous loads.. 100% for all others factoring in ambient temp. for wire sizing
----------------------
The process of calculating service conductor sizes is quite complicated and cannot be explained in the space provided here. Many qualified electricians cannot do the calculations. I'm not being critical. Most electricians have never learned the process. Even most of us who have passed the Master Electrician exam, which requires you to be able to do this, have never had to do it in the field.
The basic premise of the calculations is based on the fact that you will not run everything electrical all at the same time. Branch circuits, those that run to each piece of equipment, are sized for that equipment being on. But you would never run everything all at once. So the more circuits you have, the larger the building, the more calculating there is to do.
To answer this question the size of the cable or the amperage of the load is needed to calculate the correct wire size and connectors to fit the cable.
100 kw is the power drawn by the load. to calculate the cable size you need to know the voltage. From that you can calculate the current. this decides the cable size. for example if the voltage is 400Volts then the current flowing in the circuit when the load is 100 KW will be 250 amps. (100,000/400). for 250 amps to flow with out causing excessive heating of the cable the cross sectional area of the copper cable should be 150 sq mm.for a round cross section the diameter will be roughly 15mm.
The calculations are worked backwards from the amps used by the load of the circuit. This will be used to select the correct size of the wire. Some stipulations are added depending of the ambient temperature, length from the supply or if the load is a motor. Fusing is then dependant on the wire size that is used.
How to calculate a cable size of 3kw motor
You need to know the amperage requirement of the pump and then you can calculate the wire size.
If you know the size of the load to be served, multiply it by 125% ( times 1.25) and choose a conductor that is rated for that ampacity or higher.
To answer this question the size of the cable or the amperage of the load is needed to calculate the correct wire size and connectors to fit the cable.
Yes I could. How?
100 kw is the power drawn by the load. to calculate the cable size you need to know the voltage. From that you can calculate the current. this decides the cable size. for example if the voltage is 400Volts then the current flowing in the circuit when the load is 100 KW will be 250 amps. (100,000/400). for 250 amps to flow with out causing excessive heating of the cable the cross sectional area of the copper cable should be 150 sq mm.for a round cross section the diameter will be roughly 15mm.
4cx95mm aws which size of cable gland
take the full load current 1.732*415*I*0.85*efficiency=115*1000 => I? Depending on the value of the full load current and designed and ambient temperatures of the selected category of the cables, and voltage drop per unit length, you can determine the cable size
refer to ANSI lor..
The only way to determine the cable wire size needed for a 1000 watt air conditioner is to find the load size. To get the load size you will need to use the formula Amps = Watts or Volts. With that being said, you will need a number 14 copper wire.
The NEC has a table that shows what size cable to use with each amperage and where it can be used.
The calculations are worked backwards from the amps used by the load of the circuit. This will be used to select the correct size of the wire. Some stipulations are added depending of the ambient temperature, length from the supply or if the load is a motor. Fusing is then dependant on the wire size that is used.
for DC load and if its copper wire the cross section of the conductor wire is generally calculated as 1/4 th of the current rating . Eg for a DC load of 16 amp the copper conductor with 4 mm square is selected.
350mcm