answersLogoWhite

0

What else can I help you with?

Related Questions

What is the capacity in amperes 20 amp circuit breaker supplying a continuous load?

For a continuous load the circuit breaker is set 25% higher than the load current. So a 20-amp breaker is used with a continuous 16-amp load.


What is noncontinuous load?

A continuous load is a constant load. A noncontinuous load is one that varies over time.


What measured load can you put on an electrical panel?

If you have a measured continuous load of say 80 Amps, you would want to have a panel rated at 100 A. For continuous load you want to be at 80% of rated capacity.


What is type of breaker for 41 amp's?

For a 41 amp load, you would typically use a 50 amp circuit breaker. The general rule is to select a breaker size that is 125% of the continuous load amps or equal to the load amps if it is not a continuous load. In this case, 41 amps is considered a continuous load, so you would round up to the nearest available breaker size, which is 50 amps.


What is an electrical continuous load?

The NEC defines a continuous load as that which may run for three hours or more. Examples of these are: electric heat, water heaters, AC units, and even lighting circuits.


What is loadings?

A continuous load is a constant load. A noncontinuous load is one that varies over time.


What is the Definition continuous load?

A continuous load is an electrical load that is expected to operate continuously for three hours or more under normal conditions. It is typically used in electrical engineering to determine the capacity and ratings of electrical equipment and circuits. Continuous loads are important for ensuring safety and efficiency in electrical systems, as they affect the sizing of conductors and protective devices. When calculating load demands, continuous loads are often considered at 125% of their rated value to account for potential overloads.


What is the maximum no continuous load that can be connected to a 2AWG type THHN conductor?

The maximum continuous load that can be connected to a 2 AWG THHN conductor, according to the National Electrical Code (NEC), is typically 100 amps. However, for continuous loads, which are defined as loads that operate for three hours or more, it's advisable to apply a derating factor. This means you should limit the continuous load to 80% of the conductor's ampacity, resulting in a maximum continuous load of 80 amps for a 2 AWG THHN conductor. Always consult local codes and regulations for specific requirements.


Is the strength of a chopped strand mat CSM fiber composite always less than that of an aligned continuous fiber composite with the same volume of fibers?

That depends on the direction in wich you apply the load. If the Load is applied in the direction of the lenght of the continuous fibre this is definitely the case. However if the load is applied perpendicular on the fibre direction of the continuous fibre the CSM will be the one with the higher strenght of the two.


What is the maximum current rating for the circuit breaker if the load requires a continuous current of 25 amps?

The maximum current rating for the circuit breaker should be at least 30 amps to accommodate the continuous current of 25 amps required by the load.


How many amps can a 20 amp breaker hold on a lightning load?

I'd try to stay about 16 amps to prevent the breaker from nuisance tripping. That is as many as 32 - 60 watt incandescent (normal) lights or 83 - 23 watt CFLs. In practical terms it is hard to overload a single circuit with lights or other small loads (just about anything using a receptacle except the obvious AC unit or vacuum cleaner).


How do you claculate the secondary load of a step up transformer?

Any continuous load shouldn't exceed the rated capacity of the transformer, expressed in volt amperes.