14 gauge wire is rated for 15 amps wich is the smallest size breaker that is used in the US. I never heard of or saw a 10 amp breaker and I am a licesened electrical contractor

The 2008NEC (NFPA70) lists 16AWG copper allowed for up to a 10 amp CB, and 18AWG copper for up tpo a 7 amp CB, max current. Continuous loads must be derated to 8 amps and 5.6 amps respectively, see NFPA 70 2008, §240.4 (D) (1), (2)., but these are only going to be found in industrial applications.

Would the asked be so kind as to tell us what kind of equipment the 1 amp breaker is on?

14 AWG is still the minimum for a 15amp CB in general, this change might not be wise without an electrician looking at the entire circuit.

User Avatar

Wiki User

16y ago

What else can I help you with?

Continue Learning about Natural Sciences

Who makes a main breaker 200 amp service that has built in 200 amp gfci?

Currently, there is no manufacturer that makes a main breaker 200 amp service with built-in 200 amp ground fault circuit interrupter (GFCI) protection. GFCI protection is typically provided through individual GFCI outlets or circuit breakers installed within the electrical system.


Does anyone make a 100 amp GFCI breaker?

GFCI breakers are typically available in lower amperage ratings, such as 15 or 20 amps. 100 amp GFCI breakers are not common due to the high level of current they need to interrupt. It is more common to use GFCI protection at the branch circuit level for smaller circuits.


Can you replace your current cooker fuse 30 amp with a 40 amp circuit breaker?

A 30 amp breaker is designed to trip at an earlier point than a larger 40 amp breaker so one appliance that operates on lower amperage level could be unsafe or damaged before it could trip the higher 40 amp breaker. Also, the existing wiring may not be rated for 40 amp service.


I have a 15 amp tool hooked up to a 15 amp breaker- This trips the breaker even with nothing else running- There is also a GFCI outlet on the same circuit- Is the breaker or GFCI bad?

A 15 amp breaker will trip at 15 amps at an ambient temperature of 104 degree F. If the ambient temperature is higher the breaker will trip before 15 amps and if the ambient temperature is lower the breaker will trip after 15 amps. I would suspect the circuit is overloaded. But, you can change the breaker and see what happens. Just swap it with another one.


Do both the breakers and the outlets need to be GFI if you are running two 15 amp GFI circuits?

If you're using a GFCI breaker then the entire circuit will be protected by just the breaker alone. Every receptacle, switch, etc on that breaker will utilise the GFCI protection. You may have problems with it tripping if you plug in a motor (vacuum, etc) on the circuit.

Related Questions

What is the recommended type of breaker to use for a hot tub that requires a 50 amp GFCI breaker for safety?

The recommended type of breaker to use for a hot tub that requires a 50 amp GFCI breaker for safety is a 50 amp GFCI breaker.


What is the recommended type of GFCI 50 amp breaker for outdoor electrical installations?

The recommended type of GFCI 50 amp breaker for outdoor electrical installations is a weather-resistant GFCI breaker.


Who makes a main breaker 200 amp service that has built in 200 amp gfci?

Currently, there is no manufacturer that makes a main breaker 200 amp service with built-in 200 amp ground fault circuit interrupter (GFCI) protection. GFCI protection is typically provided through individual GFCI outlets or circuit breakers installed within the electrical system.


Does anyone make a 100 amp GFCI breaker?

GFCI breakers are typically available in lower amperage ratings, such as 15 or 20 amps. 100 amp GFCI breakers are not common due to the high level of current they need to interrupt. It is more common to use GFCI protection at the branch circuit level for smaller circuits.


Can a 4 amp breaker be used to replace a 35 amp breaker for ac unit?

NO!


How do you turn a 30 amp circuit into a 15 amp cicuit?

Replace the 30 Amp Breaker with a 15 Amp breaker.


What size amp circuit breaker should be used for a pool light?

The pool light is usually on a 15 amp circuit. The breaker feeding this circuit must have a GFCI rating.


Can I replace a 15 amp breaker with a 20 amp breaker?

No, you should not replace a 15 amp breaker with a 20 amp breaker without consulting a licensed electrician. The breaker size should match the wire size to prevent overheating and potential fire hazards.


Why does my 20 amp GFCI breaker keep tripping?

A 20 amp GFCI breaker may keep tripping due to a ground fault, overloading, or a faulty breaker. Check for any faulty appliances or wiring causing the ground fault, reduce the load on the circuit to prevent overloading, and consider replacing the breaker if it continues to trip.


What are the features and specifications of the 50 amp Eaton GFCI breaker?

The 50 amp Eaton GFCI breaker is designed to protect against electrical shocks and overloads in circuits with a 50 amp capacity. It features ground fault protection and is compatible with Eaton panels. The breaker has a voltage rating of 120/240 volts and a short circuit current rating of 10,000 amps.


What are the installation requirements for a GE 50 amp GFCI breaker?

The installation requirements for a GE 50 amp GFCI breaker include ensuring proper wiring connections, following the manufacturer's instructions, and having a dedicated circuit for the breaker. It is important to consult a qualified electrician for installation to ensure safety and compliance with electrical codes.


What are the installation requirements for an Eaton 50 amp GFCI breaker?

The installation requirements for an Eaton 50 amp GFCI breaker include ensuring proper wiring size, connecting the breaker to the power source, and following the manufacturer's instructions for installation. It is important to adhere to all electrical codes and regulations during the installation process.