Wiki User
∙ 10y agoA 15 amp breaker will trip at 15 amps at an ambient temperature of 104 degree F. If the ambient temperature is higher the breaker will trip before 15 amps and if the ambient temperature is lower the breaker will trip after 15 amps. I would suspect the circuit is overloaded. But, you can change the breaker and see what happens. Just swap it with another one.
Wiki User
∙ 10y agoIt is likely that the 15 amp tool is drawing more current than the breaker can handle, causing it to trip. The GFCI outlet might not be the issue here unless there is a ground fault causing it to trip. Consider using the tool on a circuit with a higher amperage breaker to prevent tripping.
circuit breaker and fuses used in series to break the circuit in overcurrent situation to block current to flow through circuit.
No, you cannot use an existing 8 3 wire hooked to a 30amp breaker for a heater that requires 10 2 wire. The wire gauge and breaker size need to match the specific requirements of the new heater to ensure safety and proper function. You will need to upgrade the wiring to accommodate the 10 2 wire needed for the 5000-watt 240-volt heater.
It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.
No, a standard residential breaker is typically rated at 15-20 amps in the US. A 105 amp load would require a specialized breaker or multiple breakers to handle the current. It is not safe to connect a 105 amp load to a standard single pole breaker designed for lower amperage.
Rule of thumb is about 8 unless it is a dedicated circuit. The NEC has no requirements on the number of receptacles that can be on a circuit in a residential setting. The circuit should be layed out to only cover 500 sq. feet. A single room of 500 sq. feet, you could put as many receptacle as you want on one circuit.
The previous answer is incorrect, and I would advise that user to not give out information if they are going to give completely misguided information. The interrupting rating of a breaker is the maximum current that the breaker is designed to handle, at the breaker's rated voltage, before damage will occur to the breaker. A breaker will trip at FAR LESS than the interrupting rating, but it is extremely dangerous to expose the breaker to any situation where it will have more than the rated interruption current. the breaker is designed for. The reason some breakers are rated at 22kA instead of 10kA is because they typically have far larger conductors hooked up to them, so with the lowered impedance on the circuit there is more of a chance for the breaker to experience a higher fault current at the breaker. So electricians install 22kA breakers to handle the higher "available fault current."
The wiring to the unit is either not on the right type of breaker switch or the unit is not hooked up directly to the breaker box at all.
circuit breaker and fuses used in series to break the circuit in overcurrent situation to block current to flow through circuit.
No, you cannot use an existing 8 3 wire hooked to a 30amp breaker for a heater that requires 10 2 wire. The wire gauge and breaker size need to match the specific requirements of the new heater to ensure safety and proper function. You will need to upgrade the wiring to accommodate the 10 2 wire needed for the 5000-watt 240-volt heater.
Just use one of the hot wires and cap the other. Since you are changing the breaker, the unused line will not be hooked to anything. There is really nothing to be gained by pulling new wire.
No, the battery is part of it's circuit. In fact nothing in the car will work without the battery.
parallel circuit
parallel circuit
No. circuit breakers are in series with whatever lines they are protecting. They are never put in parallel with the protected loads (this would defeat the purpose). Circuit breakers open resulting in an open circuit / no power to outlets when they trip.
Your question is confused. A galvanometer is an instrument, it is not hooked to an instrument. It is hooked to an electrical circuit of some kind, to measure how much electricity is flowing.
It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.
No, a standard residential breaker is typically rated at 15-20 amps in the US. A 105 amp load would require a specialized breaker or multiple breakers to handle the current. It is not safe to connect a 105 amp load to a standard single pole breaker designed for lower amperage.