Sure but go for a 200 amp box if you are certain your incoming power supply cable from the street can support it. You should always check with your local electric power company before you upgrade any main supply panel or breakers.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
=== === === === === ===
Chat with our AI personalities
No, a 125 amp breaker box cannot directly replace a 100 amp breaker box. The electrical panel must be properly sized to match the service size and equipment connected to it. A licensed electrician should be consulted to determine the appropriate size and make any necessary upgrades.
You would have to ensure that the service entrance cable can support 100A. Depending where you are located, you should inquire of your electricity provider if you are equipped for 100A. It may also require a meter change out.
No, it is not recommended to replace a 35 amp breaker with a 40 amp breaker for an AC unit. Breakers are designed to protect the circuit and the equipment, so using a higher rated breaker can lead to overheating and potential damage. It is best to use the correct amperage rated breaker for the equipment.
No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
If a 100 amp breaker keeps tripping there is an overload on the system.
Yes, a 100 amp main panel can have 2 separate 50 amp circuits protected by 50 amp breakers. This configuration allows for two separate circuits drawing up to 50 amps each from the main panel without overloading the panel's 100 amp capacity.
For a 41 amp load, you would typically use a 50 amp circuit breaker. The general rule is to select a breaker size that is 125% of the continuous load amps or equal to the load amps if it is not a continuous load. In this case, 41 amps is considered a continuous load, so you would round up to the nearest available breaker size, which is 50 amps.