No, the electrical code only allows #1/0 conductors and larger to be paralleled.
Chat with our AI personalities
Yes, you can run parallel wires to feed a 100 amp breaker. However, it is important to follow local electrical codes and regulations when doing so. It is recommended to consult with a licensed electrician to ensure the installation is done safely and correctly.
This is a condition that should not happen under normal conditions. In North America the smallest home breaker is 15 amps. If a fault current is higher that the breaker setting the breaker will trip.The only way the breaker could have tripped is, if when screwing the bulb out, the feed wires feeding the light socket turned and shorted out against each other.Turn the power feed off and thoroughly check the feed wires. Make sure that the insulation is good all the way to the terminal points.As a side note, if the circuit that the fixture is connected to is fully loaded to say 13 amps it would only take an additional 2 amps to trip the breaker. If the bulb flashed when you started turning the bulb out, this is most likely what happened.
On a 15 amp household breaker there is no terminal on the in feed of the breaker. The breaker either plugs into the distribution panel's bus bar or it bolts to the distribution's bus bars. The feed conductor connects to the load side of the breaker at its terminal lug.
It is generally not recommended to run an additional breaker panel in parallel with an existing one. This can create potential safety hazards, overload circuits, and violate electrical codes. It is best to consult with a licensed electrician to properly assess the situation and determine the best course of action.
To determine the amps of a breaker box, look at the main breaker or label inside the panel. The number on the main breaker indicates the maximum amperage that the breaker box can handle. Make sure not to exceed this amperage to prevent electrical hazards.
no, load will brake at 30 not 15 as needed