answersLogoWhite

0


Best Answer

Answer for USA, Canada and countries running a 60 Hz supply service.

Yes, you have to have a ground rods connected to the system. This is especially important in North American systems as a split phase is in use. The center-point winding by code must be grounded. This is a backup in case the neutral conductor becomes open. If this backup was not in place, due to the configuration of the distribution panel, 240 volts could be applied across two 120 volt loads which would be a series connection. If the resistance across both of these series loads is equal nothing will happen as the voltage drop would be even at 120 volts. If the series load resistances are not even then uneven voltage drops will appear. This could cause higher that allowed current to flow through devices that would damage them. Periodic maintenance of the ground rod connections should be done by every homeowner to make sure the connections are clean and tight.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

AnswerBot

5mo ago

Yes, a subpanel must have a separate grounding conductor running back to the main panel to provide a safe path for electrical faults. This grounding conductor is in addition to the neutral conductor and helps prevent the possibility of electric shock and ensures proper operation of circuit protection devices in the event of a short circuit.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

There should be a ground between the sub panel and the main panel, but DO NOT bond neutral to ground at the sub panel, only at the main panel. There should be a screw or metal strap that does the bonding.

This answer is:
User Avatar

User Avatar

Wiki User

15y ago

Yes, if the sub panel has more that two circuits from it and is not part of the original building that houses the main distribution panel.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Does a sub panel need a ground conductor from main panel?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What do you need and how can you install a ground cable if your 240V outlet doesn't have a ground wire?

You will need a ground rod, ground wire, and grounding clamp. To install a ground cable, drive the ground rod into the soil near your outlet's location, then securely attach the ground wire to the rod using a grounding clamp. Connect the other end of the ground wire to the outlet's metal box or any existing ground wire in the electrical system.


How do you ground a plastic box ground wire attached to GCFI and ground at fuse panel. Do I need to ground at the box itself as well?

If the plastic box has a ground wire attached to the GFCI and the ground at the fuse panel, you do not need to ground the box itself. As long as the ground wire is connected to the GFCI and the fuse panel, the box will be effectively grounded. Just ensure that all connections are secure and properly fastened.


How do you connect the wires for a 200 amp sub panel to a 200 amp main panel?

You will need to install a 4-wire feeder cable between the two panels. The two hot wires will connect to the main breaker in the main panel, the neutral wire to the neutral bus bar, and the ground wire to the ground bar. Make sure to follow local electrical codes and regulations. If you are unsure, consult with a qualified electrician.


Does the ground wire on a 200 amp panel need to be looped through both ground rods?

No, the ground wire on a 200 amp panel does not need to be looped through both ground rods. The ground wire typically needs to be connected to the grounding electrode system, which may include ground rods, but it does not need to loop through them. It is important to follow local electrical codes and guidelines when installing grounding systems.


How would you extend underground wire to your panel currently aluminum wire run to panel about 300ft I need to extend this to a new shop with a 100 amp panel 50 extra feet?

To extend the underground wire to your new shop, you would need to run a new wire from the existing panel to the new shop location. Ensure you use the appropriate wire size for the distance and amperage load (100 amps) to meet building codes and safety standards. It is recommended to hire a licensed electrician to perform this work to ensure it is done correctly and safely.

Related questions

How do you make floating ground in 100 amp sub panel Sub panel 30' from main panel and is grded to 2nd 10' rod wired to 1st 10' rod at the main panel. GFCI bkrs are nuisance tripping in bsmt location?

If the sub panel is in the same building remove the bonding screw that bonds the neutral bar to the panels enclosure. Remove the ground from the second ground rod. The sub panel is grounded by the ground wire from the sub panel's feeder. If the panel is separate from the main building treat the sub panel as a separate service. It will need its own ground rods and ground wire from the rods to the neutral bar of the sub panel. Leave the bonding screw in. There will be no ground wire in the conduit between the two services.


What do you need and how can you install a ground cable if your 240V outlet doesn't have a ground wire?

You will need a ground rod, ground wire, and grounding clamp. To install a ground cable, drive the ground rod into the soil near your outlet's location, then securely attach the ground wire to the rod using a grounding clamp. Connect the other end of the ground wire to the outlet's metal box or any existing ground wire in the electrical system.


Why would you have 115 vac on my neutral bus in the panel that has a separate ground buss?

Certainly your neutral bus is not properly bonded to the ground buss and grounding electrode conductor. But the size of your voltage worries me. You need a competent electrician to check this one for you.


Where do you ground on 100 amp panel?

A typical panel has three large wires entering the main panel from the electric meter and a bare ground wire. Two of the large wires are hot and go to the busses where the breakers are mounted. The third wire is common and is connected to one or more common bus locations. It will usually be silver in color with a screw on top to connect white wires from branch circuits. The ground is the metal of the panel itself and there will be one or more ground busses usually copper colored that are connected to the metal of the panel by screws there by "bonding" these ground busses to the metal of the panel. You should also see a copper wire coming from a ground rod connected to the metal of the panel. At the main panel you need to bond the common to the ground. There is usually a screw that allows this bonding to occur. If you have subpanels ground and common are NOT connected at the subpanels.


What wire size do you need for a 125 amp panel with a 100 amp main breaker?

A #3 copper conductor with an insulation factor of 90 degrees C is rated at 115 amps. Even though the panel is rated at a higher amperage it is the main breaker that governs the wire size.


Do you need a grounding rod at a subpanel on a detached building?

Yes. The panel must be grounded with its own grounding rod. The ground will not be provided with the feeders to the panel, these will only contain your phase wires and neutral. Also make sure that any subpanel installed does not have the neutral bonded to ground. This should only be done at the main panel where the electrical utility service is connected.


Is the voltage on a 120 volt fluorescent lighting circuit the same from line to neutral and line to ground?

Yes, to the precision you can measure it. If it isn't you need to check the ground to neutral bonding at main panel and check the wiring in the circuit for loose connections.


How do you ground a plastic box ground wire attached to GCFI and ground at fuse panel. Do I need to ground at the box itself as well?

If the plastic box has a ground wire attached to the GFCI and the ground at the fuse panel, you do not need to ground the box itself. As long as the ground wire is connected to the GFCI and the fuse panel, the box will be effectively grounded. Just ensure that all connections are secure and properly fastened.


How do you connect the wires for a 200 amp sub panel to a 200 amp main panel?

You will need to install a 4-wire feeder cable between the two panels. The two hot wires will connect to the main breaker in the main panel, the neutral wire to the neutral bus bar, and the ground wire to the ground bar. Make sure to follow local electrical codes and regulations. If you are unsure, consult with a qualified electrician.


Does the ground wire on a 200 amp panel need to be looped through both ground rods?

No, the ground wire on a 200 amp panel does not need to be looped through both ground rods. The ground wire typically needs to be connected to the grounding electrode system, which may include ground rods, but it does not need to loop through them. It is important to follow local electrical codes and guidelines when installing grounding systems.


Before installing the metal distribution boxes an electrical technician will need to remove the electrical bonding of the neutral and ground?

Conductor


How do you connect 200amp from main panel to sub panel to the lug of the min panel to lug of sub panel?

Not exactly sure what your question is and you need to make sure you are in compliance with electrical code for your jurisdiction. But, generally speaking you install a large breaker (let's say 100A 2 pole breaker to power the sub panel) just as you would install any other breaker in the presently used (hot) panel, and the proper sized cable then goes from old to new and terminates on the main lugs of the new panel. Ground and neutral are usually isolated from each other in the sub panel but depends on other factors as to location of the sub panel, etc.