the wires coming off double pole will give you 240 volts,110 each the black and white hook to these,doesn`t matter which way,ground to ground
Ground is always ground, Black and white are your two "hots." You will need a dedicated circuit, you cannot run this off existing 120V wiring. A 15A 240V circuit should be more than sufficient. If this is a permanent instalation you can use 14/2 wire as you normally would, and wire it as you normally would with the exception of the 240V breaker. If you install switches, timers, etc. Make sure they are all rated for 240V. Remember, you can't just mix-and-match between 120 and 240V. 240 appliances will not run on 120 and 120 appliances will burn up on 240.
You don't say "turn off" or turn on". Light should be connected black to black and white to white and ground to ground. If you connect white to ground it will work, but you are then using the ground wire for an unintended purpose. Neutral is bonded to Ground at the panel. Current on ground wire could cause ground loops and may cause GFCI to trip if you have them in your house.
480 lumens may not be sufficient for a flood light, as flood lights are typically used for wide area illumination and require higher lumen output. Consider a flood light with a higher lumen rating for better coverage and brightness.
You would need to check for other lights on the same circuit or switch, but it would seem to me that you have power coming into the box (black and white) and a power out going to another box or light. You would use wire nuts to connect the black and white wires from your floodlight to the existing ones.
If there are two black wires, it's possible that it was wired for a ceiling fan and that one of the wires is for the fan part while the other is for the light part. If so, one of the black wires may be switched while the other is always "on." Normally black is "hot" and white is "neutral" (NOT ground... ground is usually green).
If your house wiring is encased in armoured (metal) sheathing back to the panel, then you can secure the green ground to the ground screw in the box. Make sure the armoured cable connector is tight on the box. This should ground the light back to the panel. If you are on "knob & tube" I would suggest thinking about re-wiring the house.
The Malibu 4-Light Black Metal Flood Kit are made up of Four 50 Watt floodlights.
Yes, the Malibu 4-Light Black Metal Flood Kit comes with bulbs Low Voltage kit.4-CL1, 50 watt floodlights,100 Ft. cable etc.
flood.
You don't say "turn off" or turn on". Light should be connected black to black and white to white and ground to ground. If you connect white to ground it will work, but you are then using the ground wire for an unintended purpose. Neutral is bonded to Ground at the panel. Current on ground wire could cause ground loops and may cause GFCI to trip if you have them in your house.
Yes. Connect Black to Black, White to White and bare ground wires together.
Red is positive black is ground.
Usually, yes.
480 lumens may not be sufficient for a flood light, as flood lights are typically used for wide area illumination and require higher lumen output. Consider a flood light with a higher lumen rating for better coverage and brightness.
A "spot" is more narrow than a "narrow flood".
Dark Green / Black: Fuel Pump Motor + [To ECU]Black: Fuel Pump Motor Ground [TO GROUND]Black / White: Sensor Grd [TO GROUND]Dark Blue: Fuel Gauge Signal [TO INSTRUMENT CLUSTER]Black / Light Blue: Sensor Return [TO VARIOUS]Light Blue / Black: Low Fuel Out [TO ECU]
power = light green ground = black
An LED flood light uses a fraction of the power of a traditional flood light. It uses less then 1/4 the the power. They also last much longer the traditional flood lights.