Buy a 3 wire cord for your dryer.
For a 220 volt 100 amp breaker, you would typically need a wire gauge of 2/0 AWG (American Wire Gauge) or larger. It is recommended to consult with a professional electrician to ensure the proper gauge is used for your specific installation.
No, you should not install a 30 amp circuit breaker to a machine which normally requires a 20 amp supply. The circuit breaker is protecting the wire to the machine. That wire is likely only rated for 20 amps, (# 12 awg). Therefore, a 30 amp breaker could allow too much current to go through the wiring to the machine and cause the wire to burn down. Replace the 3 phase 20 amp breaker with the same amperage breaker.
I assume you mean you are wiring a 220 volt circuit. You will install a 220 volt double pole breaker of the correct size for the circuit. An example would be for an electric dryer that requires a 30 amp double pole breaker wired with 10/3 wire. You connect the Red & Black wires to the breaker. One on each screw. You now connect the White wire to the neutral bus bar in the service panel. Then connect the bare copper ground wire to the ground bus bar in the service panel. At the dryer outlet connect the black & red to the hot screws, white to the neutral, and ground to ground. They will be labeled on the back of the outlet.
Assuming there is no neutral: 1) Turn off the breaker. 2) Disconnect 1 of the 2 hot wires from the breaker and connect it to the neutral bar (Recommend phase taping the wire white :) ) Remember which wire you used as the neutral, in a home you will most likely have a black and a red. I would keep the black hot, and phase tape the red wire white. If it's not long enough you can wire nut another white wire onto it to make it reach the neutral bar. 3) Leave the breaker OFF, at the receptacle, change it to a 120 volt receptacle. Take the wire you made the neutral, and connect it to the white screw on the 120 v receptacle, and take the black to the hot. Ground to the ground screw. Make sure you phase tape the red wire at the receptacle white as well. 4) turn the breaker on 5) test the receptacle with a meter or receptacle testing device for correct wiring.
For a 5000 watt dryer, you should use 10-gauge (AWG) copper wire with a 30-amp circuit breaker. This corresponds to a 3-wire, 240-volt circuit with a ground wire. Make sure to consult your local electrical codes and a licensed electrician for accurate installation.
No. A 20 amp breaker needs 12 gauge wire.
For a 220 volt 100 amp breaker, you would typically need a wire gauge of 2/0 AWG (American Wire Gauge) or larger. It is recommended to consult with a professional electrician to ensure the proper gauge is used for your specific installation.
No, you should not install a 30 amp circuit breaker to a machine which normally requires a 20 amp supply. The circuit breaker is protecting the wire to the machine. That wire is likely only rated for 20 amps, (# 12 awg). Therefore, a 30 amp breaker could allow too much current to go through the wiring to the machine and cause the wire to burn down. Replace the 3 phase 20 amp breaker with the same amperage breaker.
There is 220 volts between the two poles. If you are running 2 wires (black and white) + ground then you hook black to one pole and white to the other. Put red or black electric tape on each end of the white wire and wrap around wire for 3 inches or so next to the connection so the next person will be able to see that the wire is hot and not a neutral.
I assume you mean you are wiring a 220 volt circuit. You will install a 220 volt double pole breaker of the correct size for the circuit. An example would be for an electric dryer that requires a 30 amp double pole breaker wired with 10/3 wire. You connect the Red & Black wires to the breaker. One on each screw. You now connect the White wire to the neutral bus bar in the service panel. Then connect the bare copper ground wire to the ground bus bar in the service panel. At the dryer outlet connect the black & red to the hot screws, white to the neutral, and ground to ground. They will be labeled on the back of the outlet.
Assuming there is no neutral: 1) Turn off the breaker. 2) Disconnect 1 of the 2 hot wires from the breaker and connect it to the neutral bar (Recommend phase taping the wire white :) ) Remember which wire you used as the neutral, in a home you will most likely have a black and a red. I would keep the black hot, and phase tape the red wire white. If it's not long enough you can wire nut another white wire onto it to make it reach the neutral bar. 3) Leave the breaker OFF, at the receptacle, change it to a 120 volt receptacle. Take the wire you made the neutral, and connect it to the white screw on the 120 v receptacle, and take the black to the hot. Ground to the ground screw. Make sure you phase tape the red wire at the receptacle white as well. 4) turn the breaker on 5) test the receptacle with a meter or receptacle testing device for correct wiring.
A breaker is based on wire size, as the breaker protects the wire and not the load. This is a voltage drop question. A #3 copper conductor will limit the voltage drop to 3% or less when supplying 60 amps for 110 feet on a 110 volt system.
# 3 gauge
No, you cannot use an existing 8 3 wire hooked to a 30amp breaker for a heater that requires 10 2 wire. The wire gauge and breaker size need to match the specific requirements of the new heater to ensure safety and proper function. You will need to upgrade the wiring to accommodate the 10 2 wire needed for the 5000-watt 240-volt heater.
For a 5000 watt dryer, you should use 10-gauge (AWG) copper wire with a 30-amp circuit breaker. This corresponds to a 3-wire, 240-volt circuit with a ground wire. Make sure to consult your local electrical codes and a licensed electrician for accurate installation.
You need a 40 amp breaker for a range. From a 40 amp breaker, standard ranges have a three conductor #8 copper wire installed, terminating in a three pole four wire grounding receptacle. NEMA number 14-50R.
No, it is not safe to use a 40-amp breaker on a 220V welder with 12-3 wire. The wire size should match the breaker size to prevent overheating and potential fire hazards. In this case, a 30-amp breaker should be used with 12-3 wire for a 220V welder.