answersLogoWhite

0


Best Answer

The determining factor is that the maximum unbalanced neutral current must not exceed 20 amperes. If all circuits are on the same phase, or hot leg, you would be limited to one. That's because two 20A circuits on the same phase would cause 40A of neutral current to flow. Very bad... If you have a 240 volt Edison type service with two hot legs (typical in US homes), and you use one circuit from each hot leg, you are allowed two. If you load one or the other circuit to 20A, the maximum neutral current would be 20A. If you load both circuits to 20A at the same time, the neutral current falls to zero because the two legs balance each other out. No matter how you load the two circuits (as long as each does not exceed 20A), the neutral current will never exceed 20A. If you have three-phase power, then you are allowed three circuits, as long as they are one from each phase, for the same reason as above. Of course, all this is technically accurate, and will work, but you must also check your local electrical code, because most have some specific rules and exceptions to the above. Be legal, be safe! IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS. If you do this work yourself, always turn off the power at the breaker box/fuse panel BEFORE you attempt to do any work AND always use a meter or voltage indicator

to insure the circuit is, in fact, de-energized.

User Avatar

Wiki User

15y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

14y ago

In theory, 20 amps at unity power factor (pure resistive load, no motors or Transformers), although it is good practice to not load circuits to 100% capacity. Also consider that many loads draw more current for transients than in normal operation--for example an incandescent lamp will pull a lot more current when first turned on and when the filament breaks.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

For 120V (normal in the U.S.) it would be 20x120 = 2,400; *but* this puts the circuit breaker on the edge of trip. Normally, you would want to use 16A or less (NEC rule)

which would make 1,920 the practical long-term maximum.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

In the United States, commercial and industrial installations are limited to 13 receptacles on a 20 amp circuit, 10 receptacles on a 15 amp circuit.

There is no limit for residential installations.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

A 20 amp breaker is designed to trip when it detects a current over 20 amps. Now it takes a small but finite time to recognize this excess current and trip. So given the duration of the over current spike it could be over 20 amps for a small fraction of a second before tripping. However, given that a very sharp spike could exceed 20 amps, there is also a limit for a continuous load and this is 80% of the rated amount. In this case 16 amps continuous.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

It does not matter whether the wire is stranded or solid a #12 conductor is rated at 20 amps. Stranded wire is usually used in conduit systems as the wire is easier to pull around bends in the conduit as compared to solid wire.

This answer is:
User Avatar

User Avatar

AnswerBot

3mo ago

A 120V 20-amp circuit can safely handle up to 20 amps of load. It is important not to exceed this limit to prevent overload and potential overheating of the circuit.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

Just one 20 amp circuit per neutral on 12 AWG wire. There may be multiple devices on the circuit, but end-to-end it is just a single neutral.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How many amps can be loaded on a 120V 20amp circuit?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

How many amps does 230 watts equal is you are using 120V ac circuit?

1.9 amps


How many amps is 9.8Kw?

To calculate the number of amps, you need to know the voltage of the circuit. Using the formula Amps = Watts / Volts, if the voltage is 120V, then 9.8kW at 120V would be approximately 81.67 amps.


How many amps would a 150 watt bulb draw in a 120v circuit?

1 amp


How many amps is 9000 watts?

To calculate the amps for a given amount of watts, you need to know the voltage of the circuit. If we assume a typical household voltage of 120V, then the calculation would be 9000 watts / 120V = 75 amps.


How many watts in a 115 volt refrigerator?

How many Amps is the fridge pulling? Multiply the Amps by the 120V circuit you're plugging into and you'll get your Watts.


What is difference between 2000W and 1500W and how to find out how much powerelectricity each consumes?

To find the power will depend on the voltage the item uses. Assuming a 120 volt circuit divide the wattage by the voltage, this gives the amps used. 2000w / 120v = 16.67 amps. 1500w/ 120v = 12.5 amps used.


How many watts do you need for 26 amps?

To calculate the watts needed for 26 amps, you would multiply the amperage by the voltage. For example, if the voltage is 120V, the calculation would be 26 amps x 120V = 3120 watts.


What is the max wattage for a 120V outlet?

The maximum wattage for a 120V outlet is typically around 1800 watts. This is because the standard amperage for a 120V outlet is 15 amps, and power (watts) is calculated by multiplying voltage by amperage.


Can you use 120V 13amp draw in normal house outlet?

Your normal house outlets will be either 15 amps or 20 amps. It is suggested that you don't exceed the rating of the protecting breaker by more than 80%. That would be 12 and 16 amps respectively. It may work on 15 A circuit, but if anything else ins plugged into the same circuit it might blow.


How many amps are in 6500 Watts?

To calculate the amperage, you need to know the voltage of the circuit. If you assume a standard 120V circuit, you can use the formula: Amps = Watts / Volts. For 6500 Watts on a 120V circuit, it would be approximately 54.17 Amps.


How many amp is 4 kw?

To calculate the amperage for 4 kW, you would need to know the voltage of the circuit. However, assuming a standard voltage of 120V, you can use the formula: amps = watts / volts. Therefore, for 4 kW at 120V, the amperage would be approximately 33.33 amps.


You were given aload 2500 watts how much it draw amps?

To calculate the amperage draw, you need to know the voltage of the circuit where the 2500 watts appliance will be used. You can use the formula: Amps = Watts / Volts. For example, if it is a 120V circuit, the amperage draw would be 2500 watts / 120 volts = 20.83 amps.